6.1
Overcurrent Protection
■
Over Current Protection (OCP) is built-in and works at 105% of the rated current or higher.
However, use in an overcurrent situation must be avoided whenever possible.
The output voltage of the power module will recover automatically when the fault causing
overcurrent is corrected.
When the output voltage drops after OCP works, the power module enters a ”hiccup mode”
where it repeatedly turns on and off at a certain frequency(1.2sec typ).
6.2
Thermal protection
■
When the power supply temperature is kept above 120
℃
, the thermal protection will be
activated and simultaneously shut down the output.
The output voltage of the power supply will recover automatically when the unit is cool down.
BRFS/BRDS 6-1
2.1 Pin configuration
6. Protect circuit
Applications manual
For BRFS/BRDS series