ASTE ELECTRONIC EQUIPMENT
This product must not be treated as household waste.
This product must be disposed of at a designated waste electronic equipment collecting point.
Waste electronic equipment may not be disposed of as household waste. As a consumer, you are legally
obliged to dispose of all waste electronic equipment according to national and local regulations.
4.2. Connection and Booting
Warnings:
Adhere to the warnings hereafter before you connect the network cable and the power supply cable to the
IO-Link Wireless Master. In case of ignoring this, there is a risk of electrical shock.
•
Danger from electrical shock, SELV or PELV power supply required
•
Operate the device exclusively with 24 V DC SELV (Safety Extra Low Voltage) or PELV (Protective
Extra Low Voltage) power supply
•
Always use two separate supply lines/power supplies for 1L and 2L to supply the devices
•
Pay attention to a central grounding (FE) if two separate power supplies are used
Device Destruction and Fuse Protection:
The maximum supply current must not be exceeded and must be fused with an external fuse (16 A).
Otherwise, the risk of device destruction cannot be excluded, damage to the printed circuit board and the
connecting plug.
Connection Example With TigoBridge:
The connection example described hereafter shows a typical installation that uses a TigoBridge to connect
a wired IO-Link device via a wireless connection to the IO-Link Wireless Master.
Requirements:
•
L-Coded M12 power cable
•
D-Coded M12 communication cable
•
IO-Link Wireless Master
Connect the EtherNet cable to the M12 connector EtherNet X31 of the TigoMaster 2TH device. Then,
connect the power cable (+24 V DC SELV or PELV) to the M12 connector PWR IN X21 of the TigoMaster
2TH device.
TigoBridge:
Connect the wired IO-Link device with the cable to the W-Bridge. Then, connect the power cable (+24 V
DC SELV or PELV) to the power connector of the W-Bridge.