TigoMaster 2TH
– EtherNet/IP
User Manual
Copyright © 2021 CoreTigo Ltd.
Page
62
of
75
0x5000
Device hardware fault
Error
Exchange IO-Link Device
0x5010
Component malfunction
Error
Repair or exchange
0x5011
Non-volatile memory loss
Error
Check batteries
0x5012
Batteries low
Warning
Exchange batteries
0x5013
HMI button pressed
Notification
-
0x5100
General power supply fault
Error
Check availability of power
supply
0x5101
Fuse blown/open
Error
Exchange fuse
0x5110
Primary supply voltage overrun
Warning
Check tolerance of 1L+ voltage
0x5111
Primary supply voltage underrun
Warning
Check tolerance of 1L+ voltage
0x5112
Secondary supply voltage fault (Port
Class B)
Warning
Check tolerance of 2L+ voltage
0x6000
Device software fault
Error
Check firmware revision
0x6320
Parameter error
Error
Check data sheet and values
0x6321
Parameter missing
Error
Check data sheet
0x6350
Parameter changed
Error
Check configuration
0x7700
Wire break of a subordinate device
Error
Check installation
0x7701
– 0x770F Wire break of subordinate device 1 …
device 15
Error
Check installation
0x7710
Short circuit
Error
Check installation
0x7711
Ground fault
Error
Check installation
0x8C00
Technology-specific application fault Error
Reset Device
0x8C01
Simulation active
Warning
Check operational mode
0x8C10
Process variable range overrun
–
Process Data uncertain
Warning
Check configuration of device
0x8C20
Measurement range exceeded
Error
Check application
0x8C30
Process variable range underrun
–
Process Data uncertain
Warning
Check configuration of device
0x8C40
Maintenance required
Warning
Clean
0x8C41
Maintenance required
Warning
Refill
0x8C42
Maintenance required
Warning
Exchange wear and tear parts