8.3.2. IO-Link Wireless Master Event Codes
Event code
Description
Type
Remedy
0x0000
No malfunction
Notification
No action required
0xFF21
Communication to Wireless Device (IO-
Link Device is connected to Bridge)
Event
No action required
0xFF22
Communication loss to IO-Link Device (IO-
Link Device is disconnected from
TigoBridge)
Error
Check connection from IO-Link
Device to the TigoBridge
0xFFB1
Max Retry error, indicating a packet loss
The W-Master cannot create a message to
W- Device after MaxRetry attempts.
This error indicates that one packet failed
to be transmitted successfully. This can be
for example the result of a noisy
environment (RF-wise). It affects the PER
of the system.
Error
If the PER is too high, it would
require checking the
configuration of the system
(ranges, operating channels,
etc.).
0xFFB2
IMA timeout
The W-Master did not receive a message
from the connected W-Device within the
IMA timeout. This error indicates that the
IOLW connection failed. Possibly this
leads to "Communication loss" 0xFF22.
Error
Check connection from IO-Link
Device to the TigoBridge
Table 40
– Master Event Codes
8.3.3. IO-Link Device Event Codes (Common)
The following table lists standard IO-Link Device Event Codes. For device- specific Event Codes or
remedy, use the manual of the used IO-Link Device.
Event code
Description
Type
Remedy (common)
0x0000
No malfunction
Notification
No action required
0x1000
General malfunction (unknown error) Error
See manual of the used IO-Link
Device
0x1800
– 0x18FF Vendor-specific
-
See manual of the used IO-Link
Device
0x4000
Temperature fault
– overload
Error
Check temperature, find source
for overload
0x4210
Device temperature overrun
Warning
Clear source of heat
0x4220
Device temperature underrun
Warning
Insulate IO-Link Device