19
♦
Explanation1 (Output Bank0)
*1 The Master IPS will check voltage of backup battery only when the power is on.
Pin No.
Signal type
Signal Name
(Output Bank-0)
Explanation
1 In01
Sequence
start
Master reads the “Sequence select bit” at the start of this signal and
starts Sequence program.
2 In02
01
3 In03
02
4 In04
04
5 In05
08
6 In06
Sequence select bit
16
These 5 inputs form a binary code which is capable of selecting up to 31
sequence programs.
7
In07
Next step
Sequence step can be promoted when
“Step complete (Out12)” is ON.
8
In08
Forcing next step
Sequence step can be promoted forcibly.
9 In09
Sequence
stop
When this signal is turned ON during sequence execution, sequence will
stop. (The Judgment will be NG)
10
In10
Alarm reset
When this signal is turned ON, it will clear the alarm.
11
In11
Judgment reset
When this signal is turned ON, it will clear the judgment and data.
12
In12
QL backup input
When this signal is turned ON, it will switch NG judgment to OK
judgment.
13
In13
CH1 data request
RS-232C port1 data request to option device (CN4)
14
In14
CH2 data request
RS-232C port2 data request to option device (CN5)
15
In15
Output shift bit01
16
In16
Output shift bit02
Output Bank (Out07 to 14) select bit
These 2 inputs form a binary code which is capable of selecting Bank.
19
Out01
Master ready
Output when the Master IPS is ready.
20 Out02
Sequence
running Output when the sequence is running.
21 Out03
Alarm
Output when the alarm (Master and IPS) occurs.
22 Out04
Total
OK
Output when the judgment of all work position is OK.
23 Out05
Total
NG
Output when the judgment of one (or more) work position is NG.
24
Out06
Data flag
Output when the Master IPS stores fastening data.
25 Out07
*1
01
26 Out08
*1
02
27 Out09
*1
04
28 Out10
*1
08
29 Out11
*1
Sequence answer
bit
16
Output sequence select bit (binary code) that is input
(01 to 31).
30
Out12 *1
Step complete
Output when the operation of the step has been complete.
(“Step condition” setting is needed on Sequence.)
31
Out13 *1
No dormant spindle
Output when there is no dormant (no movement) spindle.
32
Out14 *1
Battery alarm *1
Output when the Master IPS detects low voltage of backup battery.
33
Out15
Bank input answer bit01
34
Out16
Bank input answer bit02
Output “Output Bank bit” (binary code) that is input
(00 to 03).