CL33600 Series Cylindrical Lock

11

Copyright © 2009 Corbin Russwin, Inc., an ASSA ABLOY Group company. 

All rights reserved. Reproduction in whole or in part without the 

express written permission of Corbin Russwin, Inc. is prohibited.

Tighten the inside escutcheon securely to   
the mounting plate with the Phillips flat  
head machine screws provided. 

5) Installation Instructions (Continued)

14.   Inside Eschutcheon Assembly: 

Fig.  15

a. Drill 1” hole in door for magnet.
b. Drill 1” hole in frame for switch.
c. Wire to ElectroLynx® frame harness as shown 

in wiring diagrams on following pages.

15.   Install Door Position Switch (Supplied with Product):

13. 

Connector Attachment (Exterior PCB  Assembly) 

a. Connect P3 (2-pin connector) from lockbody  

to J3 on module (Fig. 13). 

b. Connect P4 (6-pin connector) from lockbody  

to J4 on module (Fig. 13). 

Fig.  13

From Lock 

Body P3 to J3

From Lock 
Body P4 to J4

 J4

 J3

McKinney 
Electronic 

Transfer

Hinge 

Inside Face of Door

Fig.  14

#8-32 x 5/8” Long 
Phillips Flat Head 
Escutcheon Screws

Door 

Status 

Switch 

Wiegand Access

Control System 

Содержание CL33600

Страница 1: ...the lock and void the factory warranty Important The accuracy of the door preparation is critical for proper functioning and security of this lock Misalignment can cause premature wear and a lessening...

Страница 2: ...television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocat...

Страница 3: ...ntrol EAC panels The reader requires 12 or 24VDC for power and is compatible with HID iCLASS 13 56 technology The Access 600 technology is designed around Corbin Russwin s Grade 1 hardware The cylindr...

Страница 4: ...ABLOY Group company All rights reserved Reproduction in whole or in part without the express written permission of Corbin Russwin Inc is prohibited Tools Required Phillips Screw Driver Standard size F...

Страница 5: ...ges Left Open Inward LH Left Hand Reverse Bevel Hinges Left Open Outward LHRB Right Hand Hinges Right Open Inward RH Right Hand Reverse Bevel Hinges Right Open Outward RHRB 1 Verify Hand and Bevel of...

Страница 6: ...whole or in part without the express written permission of Corbin Russwin Inc is prohibited 5 Installation Instructions Continued 3 Install Latch Bolt with beveled bolt facing the strike using two 8...

Страница 7: ...rough 2 1 8 diameter hole from outside of door Be sure latch engages lock body as shown Fig 6b Important Door must remain open during installation Use door stop 6 Install Inside Spring Cassette a Feed...

Страница 8: ...win Inc an ASSA ABLOY Group company All rights reserved Reproduction in whole or in part without the express written permission of Corbin Russwin Inc is prohibited 5 Installation Instructions Continue...

Страница 9: ...Wire a Insert reader assembly and route wires through door Fig 9a b Install two 8 32 x 1 3 4 flat head screws Fig 9b c Connect pin 5 green yellow ground wire ring terminal to top right screw Fig 9c Fi...

Страница 10: ...go on only one way Do not offset connector and be sure they are completely seated 5 Installation Instructions Continued 11 Connector Attachment Interior PCB Assembly Fig 11 J1 J2 To ElectroLynx Harnes...

Страница 11: ...15 a Drill 1 hole in door for magnet b Drill 1 hole in frame for switch c Wire to ElectroLynx frame harness as shown in wiring diagrams on following pages 15 Install Door Position Switch Supplied with...

Страница 12: ...must be connected to circuit GROUND of the system s power supply PIN8 Yellow LED PIN 6 Blue RX COM PIN 4 Green Data 0 PIN 2 Red Reader POS PIN 1 Black Reader NEG PIN 3 White Data 1 PIN 5 Orange RX NO...

Страница 13: ...0 Green 4 RX NO Orange 5 RX COM Blue 6 EARTH GROUND Brown 7 LED Yellow 8 LOCK NEG Violet 9 LOCK POS Gray 10 DPS NC Pink 11 DPS COM Tan 12 Not Used CL33600 Series Lock Door Status Switch 12 24 VDC H N...

Страница 14: ...TA 1 DATA 0 RX NO RX COM READER NEG Black 1 READER POS Red 2 DATA 1 White 3 DATA 0 Green 4 RX NO Orange 5 RX COM Blue 6 EARTH GROUND Brown 7 LED Yellow 8 LOCK NEG Violet 9 LOCK POS Gray 10 DPS NC Pink...

Страница 15: ...nge Power Supply By Others Access 600 Reader Requires 12 or 24 VDC Power Electrical Access Control Panel By Others Use NC for Fail Safe Operation Lock Relay NO Fail Secure Operation DPS DPS DATA 1 DAT...

Страница 16: ...configuration See reader LED Configuration c Present proximity credential and verify LED and sounder activity d Verify valid card read at EAC Panel e Verify system operation functions i e when prox c...

Отзывы: