CL33600 Series Cylindrical Lock

3

Copyright © 2009 Corbin Russwin, Inc., an ASSA ABLOY Group company. 

All rights reserved. Reproduction in whole or in part without the 

express written permission of Corbin Russwin, Inc. is prohibited.

Total 

One-Way  

Length of  

Wire Run (ft)

Load Current @ 12VDC

1/4A

1/2A

3/4A

1A

1-1/4A

1-1/2A

2A

3A

100

20

18

16

14

14

12

12

10

150

18

16

14

12

12

12

10

200

16

14

12

12

10

10

250

16

14

12

10

10

10

300

16

12

12

10

10

400

14

12

10

500

14

10

10

750

12

10

1,000

10

1,500

10

Total 

One-Way  

Length of  

Wire Run (ft)

Load Current @ 24VDC

1/4A

1/2A

3/4A

1A

1-1/4A

1-1/2A

2A

3A

100

24

20

18

18

16

16

14

12

150

22

18

16

16

14

14

12

10

200

20

18

16

14

14

12

12

10

250

18

16

14

14

12

12

12

10

300

18

16

14

12

12

12

10

400

18

14

12

12

10

10

500

16

14

12

10

10

750

14

12

10

10

1,000

14

10

10

1,500

12

10

12VDC System

• Reader Draw = 125mA (maximum)
• 12VDC Solenoid Draw =250mA (normal state)
• Total System Draw = 375mA

24VDC System

• Reader Draw = 125mA (maximum)
• 24VDC Solenoid Draw = 150mA (normal state)
• Total System Draw = 275mA

The Corbin Russwin Access 600 TCRNE1 Series cylindrical lock is designed to interface with existing Wiegand 
Electrical Access Control (EAC) panels. The reader requires 12 or 24VDC for power and is compatible with HID 
iCLASS 13.56 technology. The Access 600 technology is designed around Corbin Russwin’s Grade 1 hardware. 
The cylindrical lock (with external DPS, Door Position Switch) comes with complete inside REX (request to exit) 
monitoring and is available in 12VDC or 24VDC. Weatherseal gaskets are also included for outdoor applications. 
The Access 600 reader provides visual (LED) and audible indication of lock state (locked/unlocked). 

Latch – Stainless steel, ½” (13mm) throw 
             Optional: ¾” (19mm) throw deadlocking  
             fire latch for pairs of doors
• Deadlocking latch prevents manipulation when door closed
• Door Thickness – 1-3/4” (44mm) to 2” (50mm) standard 
   Optional 2” (50mm) to 2-1/4” (57mm) optional
• Outside lever controlled by reader or key retracts latch
• Inside Lever produces REX (request to exit) signal
• Fail Safe or Fail Secure operation (must specify)
• UL fire listed
• Wire from EAC Panel to door must be shielded with a drain. 
   Drain terminated at EAC Panel controller
• Complete monitoring of door (External DPS supplied)
• Wires directly to EAC Panels
• Accepts all HID standard iCLASS bit formats
• QC12 Hinge with ElectroLynx plug and play

2) General Description

3) Specifications / Features

Wiegand Access

Control System 

McKinney 
Electronic 

Transfer

Hinge 

Door 

Status 

Switch 

Wire Gauge Charts

Patent Pending

Содержание CL33600

Страница 1: ...the lock and void the factory warranty Important The accuracy of the door preparation is critical for proper functioning and security of this lock Misalignment can cause premature wear and a lessening...

Страница 2: ...television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocat...

Страница 3: ...ntrol EAC panels The reader requires 12 or 24VDC for power and is compatible with HID iCLASS 13 56 technology The Access 600 technology is designed around Corbin Russwin s Grade 1 hardware The cylindr...

Страница 4: ...ABLOY Group company All rights reserved Reproduction in whole or in part without the express written permission of Corbin Russwin Inc is prohibited Tools Required Phillips Screw Driver Standard size F...

Страница 5: ...ges Left Open Inward LH Left Hand Reverse Bevel Hinges Left Open Outward LHRB Right Hand Hinges Right Open Inward RH Right Hand Reverse Bevel Hinges Right Open Outward RHRB 1 Verify Hand and Bevel of...

Страница 6: ...whole or in part without the express written permission of Corbin Russwin Inc is prohibited 5 Installation Instructions Continued 3 Install Latch Bolt with beveled bolt facing the strike using two 8...

Страница 7: ...rough 2 1 8 diameter hole from outside of door Be sure latch engages lock body as shown Fig 6b Important Door must remain open during installation Use door stop 6 Install Inside Spring Cassette a Feed...

Страница 8: ...win Inc an ASSA ABLOY Group company All rights reserved Reproduction in whole or in part without the express written permission of Corbin Russwin Inc is prohibited 5 Installation Instructions Continue...

Страница 9: ...Wire a Insert reader assembly and route wires through door Fig 9a b Install two 8 32 x 1 3 4 flat head screws Fig 9b c Connect pin 5 green yellow ground wire ring terminal to top right screw Fig 9c Fi...

Страница 10: ...go on only one way Do not offset connector and be sure they are completely seated 5 Installation Instructions Continued 11 Connector Attachment Interior PCB Assembly Fig 11 J1 J2 To ElectroLynx Harnes...

Страница 11: ...15 a Drill 1 hole in door for magnet b Drill 1 hole in frame for switch c Wire to ElectroLynx frame harness as shown in wiring diagrams on following pages 15 Install Door Position Switch Supplied with...

Страница 12: ...must be connected to circuit GROUND of the system s power supply PIN8 Yellow LED PIN 6 Blue RX COM PIN 4 Green Data 0 PIN 2 Red Reader POS PIN 1 Black Reader NEG PIN 3 White Data 1 PIN 5 Orange RX NO...

Страница 13: ...0 Green 4 RX NO Orange 5 RX COM Blue 6 EARTH GROUND Brown 7 LED Yellow 8 LOCK NEG Violet 9 LOCK POS Gray 10 DPS NC Pink 11 DPS COM Tan 12 Not Used CL33600 Series Lock Door Status Switch 12 24 VDC H N...

Страница 14: ...TA 1 DATA 0 RX NO RX COM READER NEG Black 1 READER POS Red 2 DATA 1 White 3 DATA 0 Green 4 RX NO Orange 5 RX COM Blue 6 EARTH GROUND Brown 7 LED Yellow 8 LOCK NEG Violet 9 LOCK POS Gray 10 DPS NC Pink...

Страница 15: ...nge Power Supply By Others Access 600 Reader Requires 12 or 24 VDC Power Electrical Access Control Panel By Others Use NC for Fail Safe Operation Lock Relay NO Fail Secure Operation DPS DPS DATA 1 DAT...

Страница 16: ...configuration See reader LED Configuration c Present proximity credential and verify LED and sounder activity d Verify valid card read at EAC Panel e Verify system operation functions i e when prox c...

Отзывы: