5.15 Oil level control
Oil return tests are very critical for multi-evaporator applications and so
during development
testing, it is mandatory to use a Copeland Scroll Digital sample with a sight tube.
The sight
tube has graduation marks on the outside that show the oil level. However, it must be ensured
that this minimum oil is not diluted by refrigerant liquid inside the compressor. For safe operation,
the maximum oil dilution allowed is 10%. Oil dilution means the amount of refrigerant in a certain
volume of oil. Please refer to the oil dilution chart in
Figure 25
to ensure that the Copeland Scroll
Digital compressors operate in the safe zone.
5.16 Digital system control
Due to the pulsing characteristic of Copeland Scroll Digital compressors superheat control needs
to be performed by qualified solutions in order to ensure the stability, reliability and good
performance of the system.
Currently qualified solutions are:
ALCO Gated Logic Control
o
Superheat driver: EC3-D72 / EC3-D73
o
Electronic expansion valve: EX4 / EX5 / EX6
CAREL Optimised Digital Control
o
1Tool software module
5.17 Power factor
During the loaded state, when the Copeland Scroll Digital compressor operates at full capacity,
the power factor is almost the same as with a standard scroll. However, when the scrolls are
unloaded, the power factor is lower.
S
afe
ty
in
struct
ion
s
P
ro
d
u
ct
d
es
cr
ipt
ion
Inst
all
atio
n
E
lec
tr
ica
l
c
o
n
n
ec
tion
S
tar
ting
up
&
o
p
er
atio
n
Ma
int
enan
c
e &
repai
r
Dismant
ling
&
d
ispo
sa
l