Coopra TWIN80C Скачать руководство пользователя страница 6

user instructions TWIN80C_EN 

 

 

6

 

Cascade options 

 

Power mode (default)

 

 

Both units run simultaneously. Menu parameter “o” = 1 

 

 

 
At low and at high heat demand both units run simultaneously. 
 
 

Cascade selection : menu parameter “.o” = 1

 

Heat input (gross) 

16.2 – 82.2 kW 

Heat input (net) 

14.6 – 74.0 kW 

Nominal output at 80/60ºC 

14.1 – 72.0 kW 

Nominal output at 50/30ºC 

15.6 – 75.3 kW 

Efficiency at 80/60ºC (net) 

Low load = 96.6 % 

High load = 97.2 % 

Efficiency at 50/30ºC (net) 

Low load = 106.9 % 

High load = 101.8 % 

 
When the room thermostat or space unit indicates that heat is 
required for central or under floor heating, both units will heat 
simultaneously. The Master print calculates the system flow 
temperature and divides the necessary power over both units 
equally. The speeds of both fans are automatically adapted to 
the heat required, also with the use of an on/off thermostat. 
 
When the room thermostat or space unit indicates that the 
desired temperature has been reached, the central heating 
water is no longer heated. The unit pumps will continue to run 
for a previously set time to distribute the heat evenly over the 
heating installation. 
 

Comfort mode (field adjustable) 

 

Menu parameter “o” has to be set onto the value 0 

 

 

 
At low heat demand a single unit runs independently. 
At high heat demand both units run simultaneously. 
 

Cascade selection : menu parameter “.o” = 0

 

Heat input (gross) 

8.1 – 82.2 kW 

Heat input (net) 

7.3 – 74.0 kW 

Nominal output at 80/60ºC 

7.0 – 72.0 kW 

Nominal output at 50/30ºC 

7.8 – 75.3 kW 

Efficiency at 80/60ºC (net) 

Low load = 96.0 % 

High load = 97.2 % 

Efficiency at 50/30ºC (net) 

Low load = 106.3 % 

High load = 101.8 % 

 
When the room thermostat or space unit indicates that heat is 
required a single unit will start-up, while the other unit remains 
stand-by. The unit priority will change each 24 hours.  
 
When the heat required is twice low fire, the second unit will be 
started as well. Both units will heat simultaneously. The Master 
print calculates the system flow temperature and divides the 
necessary power over both units equally. The speeds of both 
fans are automatically adapted to the heat required, also with 
the use of an on/off thermostat. 

 

 

Содержание TWIN80C

Страница 1: ...E000129017 user instructions TWIN80C_EN MV190805 User instructions TWIN80C Wall hung fan flue room sealed gas boiler 2006 E000129017...

Страница 2: ...G is automatically added to the combustion air The flammable gas air mixture thus obtained is fed to the burner s via a mixing chamber to be ignited at the surface of the burner s by a ceramic glow p...

Страница 3: ...g heat demand burner off C Central heating heat demand burner on P C Central heating heat demand low load water pressure A C Central heating heat demand low load chimney temperature c Central heating...

Страница 4: ...etting return mode excluded are the settings under Letter h note for entering press button 5 sec Factory setting Customised setting u 0 10V regulation 0 Regulation on temperature C 1 Regulation on boi...

Страница 5: ...the subsequent Letter in menu parameter the user must press the Set Reset button To change the Range setting in the parameter the user must press the or the button Parameter C The setting in the menu...

Страница 6: ...ating water is no longer heated The unit pumps will continue to run for a previously set time to distribute the heat evenly over the heating installation Comfort mode field adjustable Menu parameter o...

Страница 7: ...ng call the gas company The gas flow can also be blocked because the gas filter of the boiler is contaminated this is a problem for the service man The unit also lets the pump regularly run outside th...

Страница 8: ...ver of this document This document is valid for the unit in its standard version Therefore the manufacturer cannot be held liable for any damage arising from specifications that deviate from the stand...

Отзывы: