user instructions TWIN80C_EN
4
Menu structure
By pressing the set/reset button in for longer than 5 seconds, you go to the ‘mode’ menu.
To change the subsequent "Letter" parameter, the user must press the Set/Reset button.
To change the “Range” setting in the parameter, the user must press the “+” or the “–“ button.
Pressing the “+” button you will enter the “view mode” directly, starting at indicating the water pressure wth “8”.
U S E R / I N S T A L L E R S E T T I N G S (TWIN80C)
Letter Description
Range
Factory
settings
C
Heating: Max. flow temperature setting
25 – 90°C
82°C
O
Heating: Pump post-running time
01-25 min, CO=24 hour
05
P
Heating: Max. boiler output
33 – 100%
00 (100%)
h
Extended adjustments for installer (password h= )
10 – 99
10
r
Factory setting return mode; excluded are the settings
under Letter “h”
(note: for entering press “+” button 5 sec)
= Factory setting
= Customised setting
u
0-10V regulation
0 = Regulation on temperature (°C)
1 = Regulation on boiler input (kW)
0 (4)
o
Configuration of TWIN
Power configuration = 01 (input 14,6 – 74.0 kW)
Comfort configuration = 00 (input 7,3 – 74.0 kW)
01 / 00
01 (4)
S
Pump mode
00 = Software
= Always high
= Always low
00 (4)
L
View mode of Left hand side unit
8 =
Water pressure (in bar)
1 =
Flow temperature (in °C)
2 =
Return temperature (in °C)
3
= 0÷10V
4 =
Outdoor temperature (in °C)
5 =
TWIN flow temperature (in °C)
6 =
Flue gas temperature (in °C)
7 =
Flame signal (in
μ
A DC)
9 =
Last lock-out
A =
Last blocking (internal coding)
d =
r
View mode of right hand side unit
8 =
Water pressure (in bar)
1 =
Flow temperature (in °C)
2 =
Return temperature (in °C)
6 =
Flue gas temperature (in °C)
7 =
Flame signal (in
μ
A DC)
9 =
Last lock-out
A =
Last blocking (internal coding)
Note: (4) does not return to factory settings