Coopra TWIN80C Скачать руководство пользователя страница 3

user instructions TWIN80C_EN 

 

 
Display 

 
To be able to read the codes of the, open the cover in front of 
the appliance. 
 
 

A = Status  
B = Reading 
C = “+ button” 
D = “- button” 
E = Set / Reset 
F = Flame 

 
 
 
The left 7-segment LED shows the status or the menu step. 
The two right 7-segment LED's show the temperature, the 
pressure or the parameter value. 
 

What is a functional blocking?

 

During blocking operation, the display status shows a 

continuous

 indication. The regulation blocks the burner till 

blocking conditions are within certain requirements. 
Most blocking actions restore automatically in time. Some 
blocking operations need a reset of the 230V supply power or an 
action manually. 
Note that each blocking operation will stay at least with 3 
minutes anti-cycling time. 
 

What is a functional lock-out?

 

During lock-out operation, the display status shows a 

flashing

 

indication.  
Pump runs over the heating circuit (max 24 hr). 
Fan post rinses for 1 minute at 2700 rpm (some lock-outs) 
Most lock-out operations can be restored by pressing the 
‘Set/Reset’ button. It is advised to use this button not more than 
3 times in a row. Ask your installer for help. 
Note that some lock-out operations need a reset of the 230V 
supply power. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Status indication during normal operation 

Display 

Description 

Initialisation after restoration of supply power 

Reversed neutral and line 

No heat demand, stand-by 

Central heating heat demand, burner off 

C. 

Central heating heat demand, burner on 

P/C. 

(Central heating) heat demand, low load water 
pressure 

A/C. 

(Central heating) heat demand, low load chimney 
temperature 

Central heating pump post-running 

HWS burner off/ pump post running 

b. 

HWS burner on 

P/b. 

HWS, low load by water pressure 

A/b. 

HWS, low load by chimney temperature 

Frost protection burner off pump running 8C 

o. 

Frost protection burner on 3C 

C

 

FLASHING

 

Chimney sweeper function (temp display 
max/min/ionisation) 

Status indication during “blocking” mode 

(intermittent “L” for master and “r” for slave) 

Display 

Description 

Flow sensor open circuit 

1. 

Flow sensor short circuit 

Return sensor open circuit 

2. 

Return sensor short circuited 

Flue gas sensor open circuit 

Flue gas temperature > 80°C 

Flow sensor > 105°C while the burner was off 

Blocking flow temperature  
(3 minutes anti-cycling time)  

Pump test / Start function blocking / Water 
pressure 

nc 

Electronics interruption  
(manual reset by interruption of electrical supply) 

No slave connected 

b/r 

HWS right unit 

Flow / Return temperature to high 

Status indication of ”lock-out” mode (flashing)  

(intermittent “L” for master and “r” for slave) 

Display 

Description 

Boiler does not pass start temperature test  

Too many restarts 

Internal regulation fault / A/D conversion fault / 
external sensor fault /Too many restarts 

 

Fan error 

 

Gas valve error 

Flame detected with closed gas valve 

Flue gas temperature > 95°C 

Internal interlock fault 

Flow sensor > 105°C with burner on 

Too many ignition attempts during 

Gas valve connection error 

 

Содержание TWIN80C

Страница 1: ...E000129017 user instructions TWIN80C_EN MV190805 User instructions TWIN80C Wall hung fan flue room sealed gas boiler 2006 E000129017...

Страница 2: ...G is automatically added to the combustion air The flammable gas air mixture thus obtained is fed to the burner s via a mixing chamber to be ignited at the surface of the burner s by a ceramic glow p...

Страница 3: ...g heat demand burner off C Central heating heat demand burner on P C Central heating heat demand low load water pressure A C Central heating heat demand low load chimney temperature c Central heating...

Страница 4: ...etting return mode excluded are the settings under Letter h note for entering press button 5 sec Factory setting Customised setting u 0 10V regulation 0 Regulation on temperature C 1 Regulation on boi...

Страница 5: ...the subsequent Letter in menu parameter the user must press the Set Reset button To change the Range setting in the parameter the user must press the or the button Parameter C The setting in the menu...

Страница 6: ...ating water is no longer heated The unit pumps will continue to run for a previously set time to distribute the heat evenly over the heating installation Comfort mode field adjustable Menu parameter o...

Страница 7: ...ng call the gas company The gas flow can also be blocked because the gas filter of the boiler is contaminated this is a problem for the service man The unit also lets the pump regularly run outside th...

Страница 8: ...ver of this document This document is valid for the unit in its standard version Therefore the manufacturer cannot be held liable for any damage arising from specifications that deviate from the stand...

Отзывы: