Outdoor sensor
An outdoor temperature sensor (heating) must be an NTC with a resistance of 12kOhm at 25°C
(connected to terminals (3) and (4) of the green connector block)
Letter Description
Range
Factory
settings
O/b (3) Basic temperature (outdoor sensor)
10°C – 70°C
40°C (4)
O/S (3) Slope (outdoor sensor)
1- 100
20 (4)
O/d (3) Day reference temperature (outdoor sensor)
0°C – 70°C
40°C (4)
Note: (3) Active when an outside sensor is connected, Note: (4) does not return to factory settings
Adjustment heating curve (in case of an outdoor temperature sensor)
By pressing the set/reset button in for longer than 5 seconds, you go to the ‘mode’ menu.
To change the subsequent "Letter in menu" parameter, the user must press the Set/Reset button.
To change the “Range” setting in the parameter, the user must press the “+” or the “–“ button.
Parameter „C“
The setting in the menu „C“ makes the maximal heating flow
temperature (default 82°C).
O/b-value:
The setting of the minimal Heating flow temperature
(value in °C).
O/S-value :
The setting for the sloop of the curve.
( change of Flow temperature depending on the change of the
outside temperature).
O/d-value :
The setting of the flow temperature at an outside
temperature of 20°C (value in °C).
Letter in menu
Description
Range
default
C
Max. Flowtemp. for heating
25 –90 °C
82 °C
O/b
Basic temperature
10 –70 °C
20 °C
O/S
Slope
1 – 100
20
O/d
Flow temperature at outside = 20°C
0 –70 °C
20 °C
O/S=20 [default]
Parameter C=82°C [default]
Outside temperature [°C]
Su
ppl
y te
m
p
era
tu
re
[°
C]
O/d=20°C [default]
O/b=20°C [default]