Rooftop Packaged Service Manual MAINTENANCE
63
ee driving board chip error
Yes
ee is displayed
on the wired
controller
Work Normally
Replace the
mainboard
H6 DC fan error
H6 is displayed in the
mainboard 88 indicating
lamp
Is the motor phase sequence
right?
Yes
Replace the mainboard.Does it
work normally?
No
Replace the outdoor fan
Work normally
Yes
Adjust the motor
phase sequence
Is the Fan wire terminal loose
?
Tighten the fan
wiring terminal
Yes
No
No
H6 is displayed on the wired
controller
Replace the Condenser Fan Drive
Board. Does it work normally?
No
Yes