Rooftop Packaged Service Manual MAINTENANCE
57
F2 Malfunction of Condenser Temperature Sensor
Malfunction of
condenser
temperature
sensor
Check if the condenser
temperature sensor on
mainboard is inserted on the
needle stand correctly
Disconnect
the temperature sensor and
measure if its resistance is
normal
Correctly insert the
temperature sensor
on the needle stand
Replace the
temperature sensor
Replace the
outdoor
mainboard
Yes
No
No
Yes
F3 Malfunction of Outdoor Ambient Temperature Sensor
Malfunction of
outdoor ambient
temperature
sensor
Check
if the outdoor ambient
temperature sensor on mainboard
is inserted on the needle stand
correctly
Disconnect
the temperature sensor and
measure if its resistance is
normal
Correctly insert the
temperature sensor on
the needle stand
Replace the
temperature sensor
Replace the
outdoor
mainboard
Yes
No
No
Yes
Содержание CH-IRT05NM
Страница 4: ...Rooftop Packaged Service Manual PRODUCT 1 PRODUCT ...
Страница 10: ...Rooftop Packaged Service Manual CONTROL 7 CONTROL ...
Страница 12: ...Rooftop Packaged Service Manual CONTROL 9 1 2 HEATING OPERATION ...
Страница 36: ...Rooftop Packaged Service Manual INSTALLATION 33 INSTALLATION ...
Страница 39: ...Rooftop Packaged Service Manual INSTALLATION 36 CH IRT08NM CH IRT15NM ...
Страница 49: ...Rooftop Packaged Service Manual INSTALLATION 46 CH IRT15NM CH IRT15NM ...
Страница 50: ...Rooftop Packaged Service Manual MAINTENANCE 47 MAINTENANCE ...
Страница 101: ...Rooftop Packaged Service Manual MAINTENANCE 98 5 EXPLODED VIEWS AND SPARE PART LIST Model CH IRT05NM ...
Страница 110: ...Cooper Hunter International Corporation www cooperandhunter com ...