Cooper MENVIER MF200 Скачать руководство пользователя страница 9

Installing the Panel
Read all the installation instructions before commencing with the installation.
Installation of this panel must be done by a suitably qualified/trained person. The installation must
comply with IEE wiring regulations and with BS5839 part 1 1988.
The electronic components within the Fire Panel are Static Sensitive. Do not touch the electronic
components directly.

1.

Remove the front cover.

2.

Fix the metal back box to the wall using the 3 fixing holes. No 8 screws (or similar size) are 
recommended. 

3.

Interface cables may be connected into the panel either via the back cable entry slot or through 
the top cable entries, fit the plastic blanking plugs to any unused holes.

4.

The mains supply should be exclusive to the panel and double pole isolating switch should be 
provided and clearly labeled 'FIRE SYSTEM- DO NOT SWITCH OFF.' (See BS5839 part 1 1988) 
Mains cable should only enter the panel via the top or bottom left cable entries.

5.

Connect the mains cable to the Mains input terminal block. Connect Earth to the  terminal marked
(E), Neutral to the terminal marked (N) and Live to the terminal marked (L). DO NOT TURN ON 
THE MAINS SUPPLY TO THE PANEL.

6.

Connect the battery connectors to the battery. Connect the RED wire to the battery terminal 
marked RED (+). Connect the BLACK wire to the battery terminal marked BLACK (-). Ensure the 
wires are routed away from the switches.

7.

When power is first supplied, the Panel Buzzer will sound and all the LED Indicators will light for 
approximately 2 seconds. Only the green power LED should be ON. After a few seconds the 
Fault  and Power fault LED's will flash and the buzzer will beep to indicate no mains is present on
the panel. (Other fault Indicators may be flashing at this stage). If the System Fault LED is lit and 
the buzzer is on continuously, remove the (+) battery connection and follow step (6) again.

8.

Connect the front cover to the panel by locating the bottom clips in their slots and fixing the anti-
tamper screw located on top of the panel. CAUTION ELECTRIC SHOCK HAZARD :- BEFORE 
TURNING ON THE MAINS SUPPLY THE PANEL COVER MUST BE FITTED.

9.

Turn on the mains supply to the panel. The Power fault Indication should stop after a few 
seconds.

10. Carry out testing of the system.
11. Manual call points should be individually tested for correct operation.
12. Each detector should be tested.
13. If any Auxiliary outputs are used or the Class Change input is used these should also be tested 

for correct operation.

14. Check all alarm devices work correctly.
15. Details of the Fire Alarm installation should be made in this Instruction Booklet (page 2).
16. Fill in the zone Identification Label and display clearly on or next to the panel.
17. Pass all the documentation over to the end user.

Maintenance should be carried out at regular intervals. Daily, Weekly, Quarterly and Yearly tests
should be carried out. Detailed below is a summary of the Daily and Weekly tests. For full details of
all the tests please refer to BS5839 Part 1 1988.

Daily attention by the user

The panel indicates normal operation. If a fault is displayed it should be recorded in the log book 
and reported to the service organisation.

That any faults from the previous day have received attention.

Weekly attention by the user

At least one detector or call point per week is operated for correct operation, choosing a different 
zone each week. The Panel should register this fire signal and the alarms and any ancillary 
equipment should operate

The Panel indication should be checked by pressing 'Lamptest/Exit' (key3) while in the 
supervisor mode.

Any defects should be recorded in the log book and corrective action taken as soon as possible.

PAGE 9

INSTALLATION INSTRUCTIONS - continued

ROUTINE TESTING

Содержание MENVIER MF200

Страница 1: ...NAL DI SABLE POW ER FI RE FAULT FAULT SUPERVI SOR MODE SI LENCE SOUND LAMP T EST EXI T SI LENCE BUZZE R RESET SELECT SUPERVI SOR DI SABLE TEST MF400 Cooper Lighting and Security Ltd Wheatley Hall Road...

Страница 2: ...MPATIBILITY EMC 8 INSTALLING THE PANEL 9 ROUTINE TESTING 9 FAULTS 10 FUSES 10 TECHNICAL SPECIFICATION 11 FIRE ALARM SYSTEM LOG MASTER SHEET 12 THIS SYSTEM HAS BEEN INSTALLED IN ACCORDANCE WITH THE REQ...

Страница 3: ...e Disable Mode and Test Mode 2 Code Entry Silence Re Sound Alarms Select Function Disable or Test 3 Code Entry Lamp Test Exit Toggle through Functions Disable or Test 4 NONE RESET RESET PAGE 3 PANEL C...

Страница 4: ...fire condition Note Operating RESET will not clear disable information Lamp Test Exit supervisor Mode key 3 While the supervisor LED is flashing the user can perform a lamp and buzzer test All LED s w...

Страница 5: ...gh LED s representing each zone 3 When you highlight the LED corresponding to the zone to be put into Test taken out of Test press SELECT key 2 to select that zone Zone LED lit Test LED flashing 4 Eac...

Страница 6: ...t present and de activates when the panel detects a fault It operates by providing 24Vdc which can be connected directly to a 24V auxiliary device e g relay and a pull down switch to 0V It is current...

Страница 7: ...MAR724 MAR424 24V 10mA 24V 10mA PULL TO 0v DOOR RELEASE UNITS ETC RELAY OUTPUTS 240V 10A Resistive RELAY OUTPUTS 24V 1A Resistive NC C NO NO C NC C NC NO E E C NC NO 24V 10mA COIL MAR 724 MAR 424 24V...

Страница 8: ...ce is provided The cable screen of any zone interface control or alarm line should be connected directly to the corresponding terminal marked E Additional Notes On Installation For Electromagnetic Com...

Страница 9: ...is lit and the buzzer is on continuously remove the battery connection and follow step 6 again 8 Connect the front cover to the panel by locating the bottom clips in their slots and fixing the anti t...

Страница 10: ...lst in the Supervisor Mode will clear this fault Indication Alarm Fault LED Flashing This fault should be investigated immediately as it should be assumed the alarms are not operational Each alarm lin...

Страница 11: ...t Any Earth connection to low voltage system System Fault Micro contoller fault End of Line Elements Zones 22kohm Alarms 22kohm Maximum No of detectors per zone 20 24V 30 A each Maximum Alarm Load 750...

Страница 12: ...recommended that this book is maintained by a responsible executive and that every event affecting the installation should be recorded An event should include false alarms failures tests temporary dis...

Отзывы: