2.
Release and repress (key 3) to toggle through LED's representing each function.
3.
When you highlight the LED representing each function to be enabled/disabled press
'key select’ to enable/disable this function.
4.
To exit Disable Mode and leave the panel in the disable state press 'key 1' to toggle to Supervisor
Mode LED and press ‘key 3’ or ‘key 4’
5.
When a function is disabled the LED corresponding to that function will remain lit even when you
exit the Disable Mode.
6.
To reset from Disable Mode to Normal operation, press ‘keys 2-1-1-3’, repress ‘key 3’ to toggle
through LEDs to required Zone, press ‘key 2’
Disable Mode LED flashing. This will extinguish in 2 minutes.
Test Mode (key 1, key 2, key 3)
The panel allows the supervisor to test each zone individually or any combination of zones.
When a zone is put into Test Mode the buzzer will beep.
Remote signal will not operate when a fire signal is received from a zone in the test mode.
The operation of zones which are not in the test mode will function as normal.
A fire signal from a zone in test will cause the alarms to operate for a few seconds only.
To put a zone into Test Mode, the following procedure should be used:-
.
1.
Press 'key 1' to toggle the flashing LED from 'Supervisor Mode' to 'Disable Mode' to 'Test Mode'.
2.
Release and repress ‘key 3’ to toggle through LED's representing each zone.
3.
When you highlight the LED corresponding to the zone to be put into Test / taken out of Test
press 'SELECT' (key 2) to select that zone. (Zone LED lit, Test LED flashing)
4.
Each manual call point and detector on the zone in test can now be tested.
5.
When a manual call point or detector is put into a fire condition on the zone in test, the alarms
will activate for approximately 2 seconds and the zone will remain in the fire condition for
approximately 10 seconds. The panel will then automatically reset the zones, which will take
approximately 10 seconds. The panel will indicate a fire signal from a zone in test by turning on
the corresponding zone fire LED.
6.
To clear all zone fire LED's press ‘key 3’.
7.
To exit Test Mode and leave the panel in the test state press 'key 1' to toggle to Supervisor Mode
LED and press 'Lamp Test/EXIT (key 3) or press 'RESET' (key4). Zone LED lit, Test LED lit.
8.
To reset from Test Mode to Normal operation, press ‘keys 2-1-1-3’, ‘key 1-1’ (i.e. twice). Repress
‘key 3’ to toggle through LEDs to required zone, press ‘key 2’
Test Mode LED flashing. This will extinguish in 2 minutes.
Note:- Alarms cannot be put into test mode
If a manual call point or detector is left in a fire condition on a zone in test, the panel will carry out
step 5 until the fire signal is cleared.
Operating 'RESET' will not clear test information. Test information is only lost when the mains supply
and battery are disconnected or the function is re-enabled.
PAGE 5
PANEL OPERATION - continued