Standards 

Design to comply with EN54 Part 4 1996 and Part 2 

1996

Electromagnetic Compatibility EN 50130-4 1996 

Alarm Systems Part 4 EN50081-1 1992

EN61000-2-2-1994

Number of Zones

4(MF400)                    2(MF200)

Number of alarm Lines

2

Mains Input Voltage

10%-15%

Standby Duration

24Hr 

System operating Voltage

24Vdc Nominal

Indicators

Fire 

High intensity red Light Emitting Indicators (LED)

Fault

High intensity yellow LED's

Power

High intensity green LED

Fault Indications

Zones

Open and short circuit, detector removed

Alarms

Open and short circuit

Power

Mains fail, battery fault, battery charge fault.  All fuses are 

monitored.

Earth Fault

Any Earth connection to low voltage system

System Fault

Micro contoller fault

End of Line Elements

Zones

22kohm

Alarms

22kohm

Maximum No of detectors per zone 

20 (24V-30µA each)

Maximum Alarm Load

750mA 24Vdc

Auxiliary DC Output

32mA 24Vdc (Up to 100mA at the expense of Alarm Load)

Auxiliary Fault Output

24Vdc pull to 0V. Maximum 10mA

Remote Signal Output

24Vdc pull to 0V. Maximum 10mA

Standby Power source (Battery) 

One Valve Regulated (Absorption Type) Lead Acid 

12V Battery Recommenced replacement period 4 

years. Capacity 4AH (24Hr Standby) 7AH

(72Hr standby) Max current draw is 3A resistive.

Battery Recharge Period

48Hrs 

Terminal Connector Capacity

0.5mm

2

to 2.5mm

2

Dimensions

300mm X 300mm X  74mm

Panel Weight (Mass)

24Hr 4.8kg, 72Hr 6.0Kg

Panel operating temperature

-5°C to +40°C Humidity 75% (Non Condensing)

PAGE 11

TECHNICAL SPEC

Содержание MENVIER MF200

Страница 1: ...NAL DI SABLE POW ER FI RE FAULT FAULT SUPERVI SOR MODE SI LENCE SOUND LAMP T EST EXI T SI LENCE BUZZE R RESET SELECT SUPERVI SOR DI SABLE TEST MF400 Cooper Lighting and Security Ltd Wheatley Hall Road...

Страница 2: ...MPATIBILITY EMC 8 INSTALLING THE PANEL 9 ROUTINE TESTING 9 FAULTS 10 FUSES 10 TECHNICAL SPECIFICATION 11 FIRE ALARM SYSTEM LOG MASTER SHEET 12 THIS SYSTEM HAS BEEN INSTALLED IN ACCORDANCE WITH THE REQ...

Страница 3: ...e Disable Mode and Test Mode 2 Code Entry Silence Re Sound Alarms Select Function Disable or Test 3 Code Entry Lamp Test Exit Toggle through Functions Disable or Test 4 NONE RESET RESET PAGE 3 PANEL C...

Страница 4: ...fire condition Note Operating RESET will not clear disable information Lamp Test Exit supervisor Mode key 3 While the supervisor LED is flashing the user can perform a lamp and buzzer test All LED s w...

Страница 5: ...gh LED s representing each zone 3 When you highlight the LED corresponding to the zone to be put into Test taken out of Test press SELECT key 2 to select that zone Zone LED lit Test LED flashing 4 Eac...

Страница 6: ...t present and de activates when the panel detects a fault It operates by providing 24Vdc which can be connected directly to a 24V auxiliary device e g relay and a pull down switch to 0V It is current...

Страница 7: ...MAR724 MAR424 24V 10mA 24V 10mA PULL TO 0v DOOR RELEASE UNITS ETC RELAY OUTPUTS 240V 10A Resistive RELAY OUTPUTS 24V 1A Resistive NC C NO NO C NC C NC NO E E C NC NO 24V 10mA COIL MAR 724 MAR 424 24V...

Страница 8: ...ce is provided The cable screen of any zone interface control or alarm line should be connected directly to the corresponding terminal marked E Additional Notes On Installation For Electromagnetic Com...

Страница 9: ...is lit and the buzzer is on continuously remove the battery connection and follow step 6 again 8 Connect the front cover to the panel by locating the bottom clips in their slots and fixing the anti t...

Страница 10: ...lst in the Supervisor Mode will clear this fault Indication Alarm Fault LED Flashing This fault should be investigated immediately as it should be assumed the alarms are not operational Each alarm lin...

Страница 11: ...t Any Earth connection to low voltage system System Fault Micro contoller fault End of Line Elements Zones 22kohm Alarms 22kohm Maximum No of detectors per zone 20 24V 30 A each Maximum Alarm Load 750...

Страница 12: ...recommended that this book is maintained by a responsible executive and that every event affecting the installation should be recorded An event should include false alarms failures tests temporary dis...

Отзывы: