Inputs

Class Change
A pair of terminals are provided for class change. By shorting these terminals together (e.g. switch,
time clock) the alarms will sound. The panel will not indicate a fire. The alarms will cancel when the
short circuit is removed. If the short circuit is not removed the Alarms will NOT cancel.
WARNING:- NO VOLTAGE SHOULD BE APPLIED TO THIS INPUT.

Zones
MF400 provides 4 zones & MF200 provides 2 zones . The maximum number of detectors per zone
line is 20 and end of line resistors must be fitted for correct operation.
Manual call points used in the system are polarised. Use the connection details accompanying the
call points to ensure the correct polarity is used, using the terminal marked '9300'.
Detectors used in the system are polarised 24V Menvier detectors. They must be wired in
accordance with instructions accompanying the detector. Use the terminal marked '9300'.

Outputs

Auxiliary DC Output
A 24Vdc output is provided. This output is protected by a fuse which is monitored for rupture. This
output can be to used to power fire or fault auxiliary equipment. Equipment must be connect to this
output so that current will only be drawn from this output when a fire condition exists or when no fault
exists.
WARNING:- DO NOT EXCEED THE RATED OUTPUT CURRENT

Auxiliary Fault Output
This is a 'solid state' semiconductor switch which is normally operated with no fault present and de-
activates when the panel detects a fault. It operates by providing 24Vdc which can be connected
directly to a 24V auxiliary device (e.g. relay) and a pull down switch to 0V. It is current limited to
10mA.

Remote Signal Output (Auxiliary Fire Output)
This is a 'solid state' semiconductor switch which operates when the panel detects a fire. It operates
by providing 24Vdc which can be connected directly to a 24V auxiliary device (e.g. relay) and a pull
down switch to 0V.  It is current limited to 10mA. 'Class Change' and 'Sound/Silence' do not operate
this output.

Alarms
Alarm outputs are provided. ONLY polarised and suppressed equipment should be used. 
Ensure the polarity of the connections are observed at all times and end of line resistors are fitted for
correct operation.
The maximum alarm load is specified in the Technical Specification section.
Alarm devices should be spread equally across the 2 alarm circuits.
WARNING:- DO NOT EXCEED THE RATED OUTPUT CURRENT.

Options included within this panel which are not required by EN54 are, Class Change, Remote Signal
Output and Auxiliary DC output. These options cannot be used to simulate options with requirements
within EN54.

If the panel receives a fire signal from a manual call point or detector the red fire LED will light, the
panel buzzer will sound, the alarm devices will be activated and the remote signal will also activate.
The red zone fire LED will light corresponding to the zone in fire. Any new zone in a fire condition will
light.

PAGE 6

PANEL INTERFACE CONNECTIONS AND INTERFACE CONTROLS

FIRE CONDITION

Содержание MENVIER MF200

Страница 1: ...NAL DI SABLE POW ER FI RE FAULT FAULT SUPERVI SOR MODE SI LENCE SOUND LAMP T EST EXI T SI LENCE BUZZE R RESET SELECT SUPERVI SOR DI SABLE TEST MF400 Cooper Lighting and Security Ltd Wheatley Hall Road...

Страница 2: ...MPATIBILITY EMC 8 INSTALLING THE PANEL 9 ROUTINE TESTING 9 FAULTS 10 FUSES 10 TECHNICAL SPECIFICATION 11 FIRE ALARM SYSTEM LOG MASTER SHEET 12 THIS SYSTEM HAS BEEN INSTALLED IN ACCORDANCE WITH THE REQ...

Страница 3: ...e Disable Mode and Test Mode 2 Code Entry Silence Re Sound Alarms Select Function Disable or Test 3 Code Entry Lamp Test Exit Toggle through Functions Disable or Test 4 NONE RESET RESET PAGE 3 PANEL C...

Страница 4: ...fire condition Note Operating RESET will not clear disable information Lamp Test Exit supervisor Mode key 3 While the supervisor LED is flashing the user can perform a lamp and buzzer test All LED s w...

Страница 5: ...gh LED s representing each zone 3 When you highlight the LED corresponding to the zone to be put into Test taken out of Test press SELECT key 2 to select that zone Zone LED lit Test LED flashing 4 Eac...

Страница 6: ...t present and de activates when the panel detects a fault It operates by providing 24Vdc which can be connected directly to a 24V auxiliary device e g relay and a pull down switch to 0V It is current...

Страница 7: ...MAR724 MAR424 24V 10mA 24V 10mA PULL TO 0v DOOR RELEASE UNITS ETC RELAY OUTPUTS 240V 10A Resistive RELAY OUTPUTS 24V 1A Resistive NC C NO NO C NC C NC NO E E C NC NO 24V 10mA COIL MAR 724 MAR 424 24V...

Страница 8: ...ce is provided The cable screen of any zone interface control or alarm line should be connected directly to the corresponding terminal marked E Additional Notes On Installation For Electromagnetic Com...

Страница 9: ...is lit and the buzzer is on continuously remove the battery connection and follow step 6 again 8 Connect the front cover to the panel by locating the bottom clips in their slots and fixing the anti t...

Страница 10: ...lst in the Supervisor Mode will clear this fault Indication Alarm Fault LED Flashing This fault should be investigated immediately as it should be assumed the alarms are not operational Each alarm lin...

Страница 11: ...t Any Earth connection to low voltage system System Fault Micro contoller fault End of Line Elements Zones 22kohm Alarms 22kohm Maximum No of detectors per zone 20 24V 30 A each Maximum Alarm Load 750...

Страница 12: ...recommended that this book is maintained by a responsible executive and that every event affecting the installation should be recorded An event should include false alarms failures tests temporary dis...

Отзывы: