All fault conditions on the fire panel will be indicated by the 'FAULT' LED flashing, the panel buzzer
beeping and at least one other fault specific LED flashing. The auxiliary fault output will de-activate.
All faults indications will be cleared automatically if the fault is removed unless stated.
CAUTION ELECTRIC SHOCK HAZARD :- BEFORE REMOVING THE PANEL COVER THE MAINS
SUPPLY MUST BE TURNED OFF.

Specific Fault Indication

Fault/Action

Power Fault LED Flashing 

The 240V Mains supply, battery standby supply, battery charger and 
all the fuses are monitored for faults.
Check the battery is connected to the charger correctly. Check the 
Mains supply is switched on. Check the fuses for ruptures

Power LED Flashing

The Fire Panel internal power supplies are monitored for faults.
Check 240V Mains supply is turned on. Check the fuses for ruptures. 
If the problem persists contact your service company.

Zone(s) Fault LED Flashing

The zone lines are monitored for open circuit, short circuit and 
detector removed.
Check the wiring for open circuits and short circuits. All detectors in 
the system must be correctly fitted to the detector bases. Ensure the 
end of line resistors are correctly connected. If all the zone fault 
LED's are lit pressing 'RESET' whilst  in the Supervisor Mode will 
clear this fault Indication.

Alarm Fault LED Flashing

This fault should be investigated immediately as it should be 
assumed the alarms are not operational. Each alarm line is monitored 
for open circuit and short circuit. The alarm line fuses are also 
monitored for ruptures. Exceeding rated Alarm and Aux DC load may 
cause internal power faults. If the Alarm lines switch off shortly after 
operation check for alarm line over-load. Press 'RESET' whilst in 
Supervisor mode to clear the fault indication.
Check the wiring for open circuits and short circuits Ensure the end of 
line resistors are correctly connected. Check the fuses for ruptures.

Earth Fault LED Flashing

The Fire Panel will indicate an earth fault if any connection to earth 
exists in any wiring connected to the panel, other than the Mains 
supply Safety Earth. This could be caused if the any wiring insulation 
is broken, or ancillary equipment connected to the panel has a non 
safety earth connection. If the fault persists contact your service 
company.

System Fault LED on

The Micro controller has a supervisor circuit monitoring it for correct 
operation and has detected either a software or hardware fault. To 
clear this fault indication press 'RESET' whilst in the Supervisor 
Mode. If this fault persists contact your service company.

PAGE 10

FAULTS

Aux DC (250mA 250V)

Alarm 1 (1A 250V)

Alarm 2 (1A 250V)

Note.
All fuses are glass
20mm quick blow

Battery (5A 250V)

Содержание MENVIER MF200

Страница 1: ...NAL DI SABLE POW ER FI RE FAULT FAULT SUPERVI SOR MODE SI LENCE SOUND LAMP T EST EXI T SI LENCE BUZZE R RESET SELECT SUPERVI SOR DI SABLE TEST MF400 Cooper Lighting and Security Ltd Wheatley Hall Road...

Страница 2: ...MPATIBILITY EMC 8 INSTALLING THE PANEL 9 ROUTINE TESTING 9 FAULTS 10 FUSES 10 TECHNICAL SPECIFICATION 11 FIRE ALARM SYSTEM LOG MASTER SHEET 12 THIS SYSTEM HAS BEEN INSTALLED IN ACCORDANCE WITH THE REQ...

Страница 3: ...e Disable Mode and Test Mode 2 Code Entry Silence Re Sound Alarms Select Function Disable or Test 3 Code Entry Lamp Test Exit Toggle through Functions Disable or Test 4 NONE RESET RESET PAGE 3 PANEL C...

Страница 4: ...fire condition Note Operating RESET will not clear disable information Lamp Test Exit supervisor Mode key 3 While the supervisor LED is flashing the user can perform a lamp and buzzer test All LED s w...

Страница 5: ...gh LED s representing each zone 3 When you highlight the LED corresponding to the zone to be put into Test taken out of Test press SELECT key 2 to select that zone Zone LED lit Test LED flashing 4 Eac...

Страница 6: ...t present and de activates when the panel detects a fault It operates by providing 24Vdc which can be connected directly to a 24V auxiliary device e g relay and a pull down switch to 0V It is current...

Страница 7: ...MAR724 MAR424 24V 10mA 24V 10mA PULL TO 0v DOOR RELEASE UNITS ETC RELAY OUTPUTS 240V 10A Resistive RELAY OUTPUTS 24V 1A Resistive NC C NO NO C NC C NC NO E E C NC NO 24V 10mA COIL MAR 724 MAR 424 24V...

Страница 8: ...ce is provided The cable screen of any zone interface control or alarm line should be connected directly to the corresponding terminal marked E Additional Notes On Installation For Electromagnetic Com...

Страница 9: ...is lit and the buzzer is on continuously remove the battery connection and follow step 6 again 8 Connect the front cover to the panel by locating the bottom clips in their slots and fixing the anti t...

Страница 10: ...lst in the Supervisor Mode will clear this fault Indication Alarm Fault LED Flashing This fault should be investigated immediately as it should be assumed the alarms are not operational Each alarm lin...

Страница 11: ...t Any Earth connection to low voltage system System Fault Micro contoller fault End of Line Elements Zones 22kohm Alarms 22kohm Maximum No of detectors per zone 20 24V 30 A each Maximum Alarm Load 750...

Страница 12: ...recommended that this book is maintained by a responsible executive and that every event affecting the installation should be recorded An event should include false alarms failures tests temporary dis...

Отзывы: