General
The panel has 2 levels of operation. Normal Mode and Supervisor Mode.
Normal Operation
Silence Buzzer (key 5)
The user can silence the PANEL buzzer by pressing the 'SILENCE BUZZER' key (at any time), the
buzzer will then give a beep approximately every 10 seconds.
Note:- This does not silence the alarms only the panel buzzer.
Supervisor Mode Entry (key 1, key 2, key 3)
By entering a 4 digit access code the user will enter the Supervisor Mode. The access code is 2113.
By pressing the keys in the correct order the user will see the Supervisor LED flash indicating the
panel is in Supervisor Mode.
Supervisor Mode Operation -Enter supervisor mode using access code 2113 prior to carrying
out any of the following operations.
Auto time-out of supervisor mode will occur 2 minutes after last action.
RESET (key 4)
Pressing 'RESET' at any time while in Supervisor Mode will reset the panel, clearing any fire, fault or
Test Mode information. If a fire or fault exists the panel will re-enter the fire condition.
Note:- Operating RESET will not clear disable information.
Lamp Test/Exit supervisor Mode (key 3)
While the supervisor LED is flashing the user can perform a lamp and buzzer test. All LED's will light
and the buzzer will sound. This also exits the Supervisor Mode.
Silence/Sound Alarms (key 2)
While the Supervisor LED is flashing pressing 'SOUND/SILENCE' will silence or sound the alarms. If
a fire is detected on another zone the alarms will re-sound.
Note:- If the alarms are silenced and fire condition exists the panel buzzer will sound continuously.
Disable Mode (key 1, key 2, key 3)
The panel allows the supervisor to disable individual zones, both alarm lines together or the remote
signal output. When any of these functions are disabled the buzzer will beep.
Zones, when disabled will not be monitored for fires or faults.
Alarms, when disabled will not be monitored for faults, or be activated by a fire condition.
Remote signal, when disabled will not be activated by a fire condition.
To disable/re-enable any of the above functions the following procedure should be followed:-
1. Press 'key 1' to toggle the flashing LED from 'Supervisor Mode' to 'Disable Mode'.
PAGE 4
PANEL OPERATION