2.2
Necessary Tools and Instrument List for Installation
No.
Tool
No.
Tool
No.
Tool
No.
Tool
1
Handsaw
6
Copper Pipe Bender
11
Spanner
16
Leveller
2
Phillips
Screwdriver
7
Manual Water Pump
12
Charging Cylinder
17
Clamper for Solder-
less Terminals
3
Vacuum Pump
8
Pipe Cutter
13
Gauge Manifold
18
Hoist
(for Indoor Unit)
4
Refrigerant Gas
Hose
9
Brazing Kit
14
Cutter for Wires
19
Ammeter
5
Megohmmeter
10
Hexagon Wrench
15
Gas Leak Detector
20
Voltage Meter
"
: Prohibited
!
:
O
nly for Refrigerant R407C (No Interchangeability with R22)
Measuring Instrument and Tool
Interchangeability
with R22
Reason of Non-Interchangeability and Attention
(
: Strictly Required)
Use
R410A
R407C
Refrigerant
Pipe
Pipe Cutter,
Chamfering
Reamer
-
Cutting Pipe
Removing Burrs
Flaring Tool
* The f
l
aring tools for R407C are applicable to R22.
*
If using faring tube, make dimension of tube larger
for R410A.
* In case of hard temper pipe, f
l
aring is not available.
Flaring for Tubes
Extrusion
Adjustment Gauge
-
Dimensional Control
for Extruded Portion
of Tube after Flaring
Pipe Bender
* In case of hard temper pipe, bending is not
available.
Use elbow for bend and braze.
Bending
Expanding Tool
* In case of hard temper pipe, expanding of tube is
not available. Use socket for connecting tube.
Expanding Tubes
Torque Wrench
* For 1/2 in D. (12.7mm), 5/8 in D. (15.88mm),
spanner size is up 3/32 in (2mm).
Connection of
Flare Nut
*
For 1/4 in D. (6.35mm), 3/8 in D. (9.52mm), 3/4
in D. (19.05mm), spanner size is the same.
Brazing Tool
* Perform correct brazing work.
Brazing for Tubes
Nitrogen Gas
* Strict Control against Contamin
(Blow nitrogen during brazing.)
Prevention from
Oxidation during
Brazing
Lubrication Oil
(for Flare Surface)
* Use a synthetic oil which is equivalent to the oil
used in the refrigeration cycle.
* Synthetic oil absorbs moisture quickly.
Applying Oil to
the Flared Surface
Vacuum
Drying
Refrigerant
Charge
Refrigerant
Cylinder
* Check refrigerant cylinder color.
Liquid refrigerant charging is required regarding
zeot
ro
pic
refrigerant.
Refrigerant Charging
Vacuum Pump
The current ones are applicable. However, it is
required to mount a vacuum pump adapter which
can prevent from reverse f
l
ow when a vacuum
pump stops, resulting in no reverse oil f
l
ow.
Vacuum Pumping
Adapter for
Vacuum Pump
Manifold Valve
* No interchangeability is available due to higher
pressures when compared with R22.
Do not use current ones to the different refrigerant.
If used, mineral oil will f ow into the cycle and
cause sludges, resulting in clogging or compressor
failure.
Connection diameter is different; R410A: UNF1/2,
R407C: UNF7/16.
Vacuum Pumping,
Vacuum Holding,
Refrigerant Charging
and Check of
Pressures
Charging Hose
Charging Cylinder
* Use the weight scale.
-
Weight Scale
-
Measuring
Instrument for
Refrigerant Charging
Refrigerant Gas
Leakage Detector
* The current gas leakage detector (R22) is not
applicable due to different detecting method.
Gas Leakage Check
: Interchangeability with R407C.
Use tools and measuring instruments exclusive for the new refridgerant in case of direct contact with refrigerant.
#
: Interchangeability is available with current R22
!
:
O
nly for Refrigerant R410A (No Interchangeability with R22)
Содержание CHV6-36URBM
Страница 16: ...5 3 Branch Pipe for Line Branch Unit in Inner Diameter Table 5 7 Shape Branch Pipe B 10 H 11 Branch Pipe...
Страница 31: ...26 Table 8 1 Checking of Wire Connection by Test Run...
Страница 32: ...SPWT J01 27 7...