background image

W12=

W11=

1.1

5.8    Additional Refrigerant Charge

It i

s necessary to add additional 

refrigerant charge

 

as follows.

1. Calculating Method of Additional Refrigerant Charge

A.

 

Determine an 

to 

additional refrigerant quantity according to the following procedure, and charge it into the 

system.

 

B.

 

Record the additional refrigerant quantity to facilitate service activities thereafter.

Although refrigerant has been charged into this unit, it is required that additional refrigerant be charged according

 

to piping length.

See Example for Model 

CHV6-60URBM

, and fill in the following table. 

Pipe Diameter in (mm) 

Total Piping Length ft  (m) 

Additional Charge (lbs)

Total Piping  Length

    

  

16 ft

 

Total Piping Length

 

Additional

 Ref.Charge

<EXAMPLE>

W11=

CHV6-60URBM

17

a

b

 Ref.Charge

W

0

W

1

W

2

a

b

100%~130% 130%~150%

CHV6-36URBM

8.4

0.02

6

0.013

17.4

CHV6-48URBM

8.4

0.02

6

0.013

17.4

CHV6-60URBM

9.0

0.02

6

0.013

17.4

0.33lbs for

each 10%

ķ

1.32lbs for

each 10%

ķ

W0+W1+W2

NOTE:

ķ

Less than 10% is calculate

d

 as 10%.

Model

W0:

Ref.Charge

before

shipment

(lbs)

W1:

Additional

Ref.Charge according 

to piping

(lbs/ft )

W2:

Additional Ref.Charge 

according to 

Connection Ratio

(lbs)

Wt

˖

Total Ref.

Charge

(lbs)

Max. Total

Ref.

Charge

(lbs)

 

Additional Refrigerant Charge

 

according to Table 5.

9

Tab e 5.9  Additional Refrigerant Charge Calculation

W2

 

=

    

0

W2

 

=

      

 

Pipe Diameter (in ) 

 

Total Piping Length (ft ) 

Additional 

Charge

W1

2

=

Additional Refrigerant Charge Calculation

lbs

lbs

lbs

lbs

1/4

3/8

3.3

1/4

3/8

  

32.8

   

 16.4

  

 16.4

 

 16.4

 

32.8

   

32.8

   

16.4

 

 

0.02

6

2.2

 

0.0134

3/8×32.8ft

3/8×16.4ft

3/8×16.4ft

1/4×16.4ft

3/8×16.4ft

1/4×32.8ft

1/4×32.8ft

lbs

lbs

Содержание CHV6-36URBM

Страница 1: ...CHV6 36URBM CHV6 48URBM CHV6 60URBM MODEL Installation Maintenance Manual VRF AIR CONDITIONER HEAT PUMP OUTDOOR UNIT Outdoor Units ORIGINAL INSTRUCTIONS...

Страница 2: ...for large difference in temperature for changing operate mode Our company our company The air conditioning installation maintenance can only be conducted by dealers or professionals Temperature Cooli...

Страница 3: ...k or a fire Check that the ground wire is securely connected If the unit is not correctly grounded it may lead to electric shock Do not connect the ground wiring to gas piping water piping lightning c...

Страница 4: ...s liability shall not cover defects arising from the alteration performed by a customer without our company s consent in a written form NOTE It is recommended that the room be ventilated every 3 to 4...

Страница 5: ...e Space 4 4 Installation Work 6 5 Refrigerant Piping Work 8 8 8 11 12 13 14 16 17 5 1 Piping Materials 5 2 Refrigerant Piping Work 5 3 Branch Pipe for Line Branch 5 4 Piping Connection 5 5 Air Tightne...

Страница 6: ...or Heat Exchanger Propeller Fan Fan Motor Check Valve Reversing Valve Distributor Check Joint for High Low Pressure Cool Heat Strainer Electrical Expansion Valve Gas Liquid Separator 1 High Pressure S...

Страница 7: ...Temperature Sensor NO Strainer Electrical Expansion Valve Stop Valve for Gas Line Stop Valve for Liquid Line Bypass High Pressure Protect High Pressure Low Pressure Remark Gas Liquid Separator Compre...

Страница 8: ...m correct brazing work Brazing for Tubes Nitrogen Gas Strict Control against Contamin Blow nitrogen during brazing Prevention from Oxidation during Brazing Lubrication Oil for Flare Surface Use a synt...

Страница 9: ...paper Put Cloth or Paper Do not put any foreign material into the outdoor unit and check to ensure that none exists in the outdoor unit before the installation and test run Otherwise a fire or failure...

Страница 10: ...he electromagnetic wave radiator When installing the outdoor unit in snow covered areas mount the field supplied hoods at the discharge side of the outdoor unit and the inlet side of the heat exchange...

Страница 11: ...TE When the mark dimension is secured piping work from bottom side is easy without interference of foundation in 3 Example of fixing outdoor unit by anchor bolts Cut this portion when this type of anc...

Страница 12: ...r stable installation as shown in Fig 4 6 in Base Width of Outdoor Unit 2 31 32 Frame Width 2 3 8 Field Supplied Frame Incorrect Outdoor Unit is Unstable Metal Plate Metal Plate 3 15 16 or more Correc...

Страница 13: ...ap or vinyl tape Attach a cap or vinyl tape Attach a cap or vinyl bag with rubber band Do not place the pipe directly on the ground Rain water can enter 5 Refrigerant Piping Work O O O O Flaring Dimen...

Страница 14: ...ld than 100 otherwise overload operation may occur in harsh conditions or narrow range 2 100 additional charge should be reduced according to the indoor unit type 5 10 3 The capacity of indoor unit sh...

Страница 15: ...ngth Lt Total Pipe Lentth Outdoor is Higher than Indoor Unit Indoor is Higher than Outdoor Unit Indoor and Branch Pipe Max Height Distance betwen Indoor and Indoor or Max Pipe Length between Branch Pi...

Страница 16: ...5 3 Branch Pipe for Line Branch Unit in Inner Diameter Table 5 7 Shape Branch Pipe B 10 H 11 Branch Pipe...

Страница 17: ...nfirm that the valve is closed 2 Prepare a field supplied bend pipe for liquid line Connect it to the liquid valve by flare nut through the square hole of bottom base 3 For Gas Piping Connection Prepa...

Страница 18: ...efrigerant piping at certain points and prevent the refrigerant piping from touching the weak part of the building such as wall ceiling etc If touched abnormal sound may occur due to the vibration of...

Страница 19: ...t the pressure in the mani fold gauge does not increase Note This unit is only for the refrigerant R410A The manifold gauge and the charging hose should be exclusive use for R410A is not available it...

Страница 20: ...the devices will be damaged An excess or a shortage of refrigerant is the main cause of damages to the units Charge the correct refrigerant quantity according to the description of label at the insid...

Страница 21: ...Be careful that refrigerant and oil do not splash onto the electrical parts when removing the charge hoses Exclusive for Vacuum Pump and Refrigerant Charge 16 Fig 5 4 Check Joint Position 1 Maximum Pe...

Страница 22: ...Length Additional Ref Charge EXAMPLE W11 CHV6 60URBM 17 a b Ref Charge W0 W1 W2 a b 100 130 130 150 CHV6 36URBM 8 4 0 026 0 013 17 4 CHV6 48URBM 8 4 0 026 0 013 17 4 CHV6 60URBM 9 0 0 026 0 013 17 4 0...

Страница 23: ...Charge refrigerant R410A into the system as follows 1 For charging refrigerant connect the gauge mani fold using charging hoses with a refrigerant cylinder to the check joint of the liquid line stop...

Страница 24: ...10 of nominal voltage If not electrical parts will be damaged 3 Check to ensure that the capacity of power 4 Check to ensure that the ground wire is connected 5 Check to ensure that the electrical re...

Страница 25: ...l be damaged Remote Control Switch Option 3 Do not wire in front of the fixing screw of the service panel If you do the screw can not be removed NOTES 2 If total wiring length less than 98 ft 30m it i...

Страница 26: ...Switch Cable Shielded Twist Pair Cable AWG18 x 2 This cable dose not need any polarity Do not apply an excessively high voltage to this cable Rated Voltage 12V Remote Control Switch Option Remote Con...

Страница 27: ...el Install main switch and ELB for each system separately Select the high response type ELB that is acted within 0 1 second Separate the control wiring between outdoor unit CHV6 36URBM CHV6 48URBM CHV...

Страница 28: ...e installed between power supply and air conditioning unit in such a manner that the contact spacing shall not be less than 3mm 6 Once the power cord is damaged the dealer or the professionals from de...

Страница 29: ...tting Shipment I U is located higher than O U 65 ft than I U 82 ft Test Run Cool O U is located higher 24 CHV6 60URBM CHV6 36URBM CHV6 48URBM Compressor Forced Stop Digital Unit Forbid Setting Communi...

Страница 30: ...12 hours to warm the compressor oil by the oil heater Pay attention to the following items while the system is running A Do not touch any of the parts by hand at the discharge gas side since the comp...

Страница 31: ...26 Table 8 1 Checking of Wire Connection by Test Run...

Страница 32: ...SPWT J01 27 7...

Страница 33: ...eck Refrigerant Temperature Liquid Temperature o Discharge Gas Temperature o 8 Check Pressure Discharge Pressure P Suction Pressure P 9 Check Voltage Rated Voltage V Operating Voltage V Starting Volta...

Страница 34: ...able 8 3 Alarm Code T 29...

Страница 35: ...4 15 3 2 0 05 0 20 MPa A 50 W Min A 5 CHV6 36 48 60URBM Automatic Reset Non Adjustable For Compressor Pressure Switch High Pressure Cut Out Cut In Fuse on Main Circuit Compressor Crank Heater Power Co...

Страница 36: ...08 0 V01 The Company is committed to continuous product improvement We reserve the right therefore to alter the product information at any time and without prior announcement...

Отзывы: