Coolerado Installation
Page
6
of
53
unit’s intake air supply. If ducted, ensure adequate
condensate drains are available.
The intake air opening must be kept free from
obstruction and allowed to draw in fresh dry air.
The conditioned air must be unobstructed to the
building or space to be cooled.
All ductwork must be properly sealed and insulated.
Keep all ductwork runs as short as possible between
the unit and conditioned space.
If exhaust ducts are needed they must be sealed.
If unit is installed outdoors, install rain shields as
needed.
In unheated environments, provide adequate freeze
protection for system water supply and drain.
Ensure level mounting to allow the internal water
distribution to work correctly.
If the potable water supply is considered moderately
hard, hard or very hard include a sodium-based
water softener, see
Appendix 1
.
NOTE: Make any necessary duct modifications to implement
seasonal Duct Blocks during initial installation.
It is recommended that off-season duct blocking devices be
installed as part of the end-of-season shutdown procedures.
Step 1—Check Equipment and Job Site
CAUTION: Take the necessary precautions and use
appropriate equipment to move and install.
INSPECT PACKAGING OF EQUIPMENT BEFORE ACCEPTANCE
Check the unit for any signs of shipping damage before
accepting equipment from the freight carrier. If shipment is
damaged do not accept shipment or it may become yours as
is. If damaged, file an immediate claim with the shipping
company. No return shipment will be accepted without
written return authorization.
UNPACK UNIT
Move to final location. Remove carton or packaging, taking
care not to damage unit.
INSPECT EQUIPMENT
Check the unit for any signs of shipping damage. Fan should
spin freely and all covers and parts should be secured
properly. To reduce the shipping footprint on a C60, the
conditioned air plenum may be shipped wrapped to the inlet
of the unit rather than bolted on. If shipment is damaged or
incomplete, file a claim with the shipment company as soon
as possible. No return shipment will be accepted without
return authorization.
NOTE: The unit is shipped with air filters for initial use.
CHECK BUILDING UTILITIES AND GEOMETRY
Check for plumbing vent location
Check for exhaust vents and fumes from heaters
Check water location and hookup
Check for location of sanitary sewer drain
Check for storm sewer
Do downspouts connect to the storm sewer drain?
Check power
Check control connections
Check water hardness
LOCATION OF EQUIPMENT
Select a location for the unit as close as possible to the supply
air diffuser and away from any building exhaust or sources of
high humidity levels.
NOTE: If tying into existing HVAC equipment check for
complete functionality before starting any work.
NOTE: Prevailing winds and building geometry must be
taken into consideration in determining air inlet and
exhaust locations. Additional ductwork for either the intake
or exhaust may be required to assure proper separation of
the air streams.
Prevailing wind consideration, Figure 1
NOTE: Inlet hoods should not be located near driveways,
parking lots, gas meters, oil fill pipes, dryer vents or other
Содержание C60A
Страница 4: ...Page 4 of 53 Installation Notes ...
Страница 34: ...Coolerado Installation Page 34 of 53 Appendix 9 M30 Dimensional Specifications ...
Страница 36: ...Coolerado Installation Page 36 of 53 Appendix 11 M50B Dimensional Specifications ...
Страница 40: ...Coolerado Installation Page 40 of 53 C60A Dimensional Specifications Continued ...