![Coolerado C60A Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/coolerado/c60a/c60a_installation-manual_2661042012.webp)
Coolerado Installation
Page
12
of
53
NOTE: Adjust barometric dampers to optimize air
distribution.
Diffuser location examples:
Installation of a room diffuser might have the
conditioned air delivered at the opposite side of the
room from the door and sweep toward the door to a
barometric duct in the ceiling, see
Figure 17
.
A room with a window may have the diffuser
installed on the opposite side from the window, with
cooled air sweeping the room toward the window
and removing the hot air above the window, see
Figure 18
.
NOTE: Avoid sharp bends and sudden reductions in ducting
causing pressure drops which impede air-flow.
Conditioned Air Plenum Duct Connection Figure, 15
M30 and C60 Conditioned Air Plenum inside Box, Figure 16
NOTE: Set the conditioned air plenum inside the box or the
HMX frame so that water will be directed into the box
rather than to the outside. Seal outside edge at bottom of
plenum, see Figure 16.
NOTE: The conditioned air plenum is not insulated in the
factory. Insulate plenum after duct holes have been cut out.
In outside installations, the plenum should be fully insulated
and sealed to reduce air temperature increases within the
plenum. Any increase in the conditioned supply air
temperature will result in an increased building temperature
and run time.
NOTE: Barometric Dampers and /or building exhaust fans
are installed to relieve conditioned space pressure at the
highest temperature locations.
Barometric Damper Example, Figure 17
Installation Example, Figure 18
Step 8 – Working Air Ducts, (unit exhaust)
If installed outside in an area with good ventilation,
install side louvers.
Содержание C60A
Страница 4: ...Page 4 of 53 Installation Notes ...
Страница 34: ...Coolerado Installation Page 34 of 53 Appendix 9 M30 Dimensional Specifications ...
Страница 36: ...Coolerado Installation Page 36 of 53 Appendix 11 M50B Dimensional Specifications ...
Страница 40: ...Coolerado Installation Page 40 of 53 C60A Dimensional Specifications Continued ...