Step 5 – Drain Connections
NOTE: The units drain connection is located underneath the
unit’s intake air plenum.
Install system drain piping
A drain line must be connected to the:
o
M30 or C60 - 1½” (38.1 mm) ABS female slip
connection
o
M50A - can be 1 ½” (38.1 mm) pipe over
outside; 1 ¼” (31.75 mm) inside or 40mm
deeper inside
If local or state codes allow drain water to be used for
Irrigation it must be drained away from the pad to eliminate
any settling that will prevent the unit from remaining level. If
this occurs, the drain line must slope a minimum of 1/8” per
foot (10.4 mm/meter).
Pooling of water near the unit will also allow excess humidity
to be drawn into the unit, which will reduce the cooling
performance of the unit.
CAUTION: Do not discharge to roof top drains that drain to
parking lots or alleys. (The continual flow of water will cause
a slick green algae growth).
Drain Connection, Figure 10
If the unit drain line is connected to an internal building
sanitary sewer drain line, it must feed into a 1-1/4” (40mm),
(or larger) plumbing drain line that meets all plumbing code
requirements. The drain line must be vented as it enters the
building sanitary sewer drain line.
Step 6—Outdoor Intake Air
NOTE: The intake air duct must not be located near the units
working air duct.
Install and inspect ductwork if needed.
The intake air can enter the unit directly or through a
properly sized duct. Use intake sizes from
Table 1:
Model
Intake Duct Size
Intake Duct Size
M30
16 inches, (20” at fan inlet)
400 mm, (508 mm
at fan inlet)
M50
20 inches
500 mm
C60
22 inches, (20” at fan inlet)
560 mm, (508 mm
at fan inlet)
Intake Duct Sizes, Table 1
NOTE: If the unit is installed in a building (attic or other) a
duct may be needed to draw fresh intake air into the unit
from outside the building.
NOTE: The free open area of the intake grill must equal the
duct area. Failure to do so may cause excessive pressure
drop across the grill, see duct sizes in Table 1.
NOTE: If rigid duct is used to connect to the unit’s intake air,
it must be designed to be easily removed to allow service
access.
NOTE: In some roof top installations, parapet walls can trap
the heavy cool humid working air below the walls causing
the intake air to have a high humidity resulting in higher
conditioned air temperatures. In these situations the intake
air may need to be brought from a higher location, see
Figure 11.
High Parapet Walls, Figure 11
Содержание C60A
Страница 4: ...Page 4 of 53 Installation Notes ...
Страница 34: ...Coolerado Installation Page 34 of 53 Appendix 9 M30 Dimensional Specifications ...
Страница 36: ...Coolerado Installation Page 36 of 53 Appendix 11 M50B Dimensional Specifications ...
Страница 40: ...Coolerado Installation Page 40 of 53 C60A Dimensional Specifications Continued ...