Exhaust Louvers, Figure 21
M50A and C60 units are shipped with precut holes for
louvers. The M30 units require that holes be cut to accept the
louvers. Side louvers should be cut low in the box so the
heavy working air falls away from the intake air.
To install these louvers in an M30, cut a 16 “ x 16 “ (406 mm x
406 mm) hole on one or both sides of the unit.
NOTE: One side is sufficient to allow for working air exhaust
on an M30 model, but two (2) are required for the M50A’s
and C60’s.
CAUTION: The working air expels excess water, minerals and
salts at all times it is in operation. Any holes cut into this
section or screws attached must be coated on the inside
with a high quality duct sealer to prevent corrosion. In most
cases the HMX’s will need to be removed to adequately seal
any punctures to the inside of the working air section and
prevent rusting of the box. This may void warranty if not
properly sealed.
Side Cover and Louver Attachment:
To seal the side covers or louver very little torque is needed
to tighten the screws. Over tightening will cause warping of
the cover or louver. Eight (8) 10 – 32 stainless steel screws
are used to hold the louvers or covers on. The unit comes
with matching blind rivets mounted in the box.
Inside Cover, Figure 22
Step 9 – Water Supply Connections
Note: Do not turn water on unit till Step 15.
See
Appendix 14
for line size and pressure charts.
CAUTION: Clean potable water should be connected to the
Coolerado air conditioner, see
Appendix 1 Coolerado Water
Quality Requirements
for more details.
Water lines should be insulated from heat sources such as the
sun to prevent overheating and scaling of the water. If the
water line insulation will see sun light at any point it should
be UV protected material. When hard water is heated, it
increases its scaling potential such as in a water heater.
NOTE: When choosing to insulate exposed water lines, UV
protection must be accounted for. If using non-UV rated
insulation, it is suggested to coat the insulation with a
weatherproofing finishing paint or jacket.
The instantaneous water flow rate to the HMX’s is the water
required when turned on by the water control board. The
water is turned off most of the time. A clean and consistent
water supply capable of instantaneous, dynamic flows of 51
GPH (gallons per hour) (193 LPH (liters per hour)) will be
required for the model M30, 85 GPH (322 LPH) M50, and 102
GPH (386 LPH) C60, for proper operation of the units.
NOTE: Install a hose bib at the main water line near the unit.
This will allow for quicker and easier servicing as well its
double use for cleaning the units.
Содержание C60A
Страница 4: ...Page 4 of 53 Installation Notes ...
Страница 34: ...Coolerado Installation Page 34 of 53 Appendix 9 M30 Dimensional Specifications ...
Страница 36: ...Coolerado Installation Page 36 of 53 Appendix 11 M50B Dimensional Specifications ...
Страница 40: ...Coolerado Installation Page 40 of 53 C60A Dimensional Specifications Continued ...