ASCII I/F
CoolMasterNet PRM Rev 0.7
18
www.coolautomation.com
© 2017 CoolAutomation
·
Line is a CooLinkNet HVAC Line number in range L1..L4. L* means "any line". In some cases to provide
backward compatibility Line can be omitted from the UID.
·
Dot is a separator between Line and Indoor Number. If Line is omitted or has a L* form, dot must also be
omitted.
·
Indoor Number is an Indoor Unit number in HVAC system. Indoor Number can be '*' that means "any"
Examples:
L1.102
Indoor Unit 102 on line L1
L2.003
Indoor Unit 003 on line L2
L*100
Set of Indoor Units 100 on all lines
L3.1*
Set of Indoor Units 1xx on line L3 (L3.100, L3.101, ... )
L4
All Indoors on line L4
L*
All Indoors on all lines
203
Similar to L*203 (for backward compatibility only)
UID_STRICT
In some cases only specific Indoor Unit should be referenced by UID. In this case it is required to use
UID_STRICT in format Ln
.
XYY where '*' usage is prohibited.
6.2 Commands Reference
Synopsis and description of the commands listed below have the following notation:
·
Parameters or parameters group in angle brackets < > are mandatory.
·
Parameters or parameters group in square brackets [ ] are optional and can be omitted.
·
The curly braces ( ) are used to denote group inside braces
·
The | character between parameters inside brackets means OR.
6.2.1 Configuration Commands
set
line
ifconfig
boot
sddp
knx
props
link
plug
hdl
set
SYNOPSIS
set [<SETTING> <VALUE>]
set defaults
DESCRIPTION
Query or change CoolMasterNet setting(s). Without parameters
s e t
command will list all supported settings