ASCII I/F
CoolMasterNet PRM Rev 0.7
26
www.coolautomation.com
© 2017 CoolAutomation
L1.102 | - | 0 | c d f h a | l m h a |
L2.107 | - | 1 | c d f h a | l h |
L1.101 | - | 1 | c f hx | l m h a |
OK
link
SYNOPSIS
l i n k
link delall
link -L
link ram R
link <
>
DESCRIPTION
Control link operation in CoolMasterNet. Linking ThermoPad on
line with Indoor Unit will grant the
ThermoPad full control over the Unit.
·
In format without parameters l i n k will list existing links
·
link delall - delete all links
·
link -L - delete link number L (link numbers displayed in the list of existing links)
·
link ram R - create link Data Base for R groups. The operation will take effect after reboot. Use this
operation only if default link Data Base is too small.
·
link <
> - create new link, where UID1 is ThermoPad on
line and UID2 is Indoor Unit. The command generate invisible
for one of the UID's. <=|~> defines link
type: = regular link, the ThermoPad will become invisible; ~ link with haux mode usage, the Indoor Unit will
become invisible. Regular link will allow to control the Indoor Unit through UID2, while haux link through UID1.
EXAMPLE
List existing links
>
link L3.082=L1.101
L000: L3.081 <--> L7.096
L001: L3.083 <--> L1.100
OK
Delete link number 0
>
link -0
OK
Link ThermoPad 082 on line L3 with Indoor Unit 101 on line L1 (regular link)
>
link L3.082=L1.101
OK, Boot Required!
Link ThermoPad 080 on line L3 with Indoor Unit 100 on line L1 (haux link)
>
link L3.080~L1.100
OK, Boot Required!
Delete all links
>
link delall
OK
Create link Data Base for 60 links
>
link ram 60
OK, Boot Required!
plug
SYNOPSIS
plug <