ASCII I/F
CoolMasterNet PRM Rev 0.7
23
www.coolautomation.com
© 2017 CoolAutomation
·
Without parameters, if SDDP module was enabled and Ethernet cable connected, sddp command will list
supported protocol version and packet counters.
·
sddp enable - persistently enables SDDP module (effective after reset). Default state.
·
sddp disable - persistently disables SDDP module (effective after reset)
·
sddp identify - sends IDENTIFY message to Control4® Composer tool to add CoolMasterNet to the
current project
·
sddp offline - signals that CoolMasterNet is going offline
·
sddp alive - signals that CoolMasterNet is online
EXAMPLE
Enable SDDP module
>sddp enable
OK, Boot Required!
Send IDENTIFY message
>sddp identify
OK
knx
SYNOPSIS
knx
knx addr <area/line/device>
knx ram <R>
knx funcs
knx group
knx group <GA>[ <func> <direction> <
> ]
knx group dellall
knx group -<G>
DESCRIPTION
Query or change KNX status and configuration. In format without parameters knx command will provide
information about current connection status and number of used groups.
·
knx addr <area/line/device>
- Set KNX physical address in the form of area/line/device
·
knx ram <R>
- Create group Data Base for R groups. The operation will take effect after reboot. Use this
operation only if default group Data Base is too small. The current Data Base usage can be seen in knx
command.
·
knx funcs
- Print all available group functions.
·
knx group
- List existing KNX groups (linkage status)
·
knx group <GA>
- List existing KNX groups (linkage status) for the given group address
·
knx group <GA> <func> <direction> <
- Create new KNX group, i.e. link KNX group
address <GA> with CoolMasterNet function and UID. <GA> can be in the form of Main/Mid/Sub or Main/Sub,
direction: < - CoolMasterNet input, > - CoolMasterNet output.
·
knx group dellall
- Delete all KNX groups
·
knx group -<G>
- Delete KNX group number <G>. Group numbers displayed in the list of existing
groups.
SUPPORTED FUNCTIONS
Name used
in command
Full name
Values
Data
type
Can be sent to
CoolMasterNet
Can be sent
from
CoolMasterNet
onoff
On/Off
0 - off, 1 - on
1.001
P
P
ST
Set temperature
float value according to data
9.001
P
P