PoolWarden Manual www.poolwardentraining.com 530-205-4520 35
Alarm Out Control Type
Alarm Out is where an external alarm can be connected to an Auxiliary Relay
and configured in this menu. This may be needed in cases where a more
pronounced sound or light is needed.
On if Alarm On - Yes
Off if Flow Off - 1
Alarm Out
⧫
On if Alarm On - Yes:
When set to Yes the Aux relay will be on if the alarm light is on.
⧫
Off if Flow Off - 1
: The relay will be turned OFF if “No Flow” is detected in Flow Switch Input 1. Press
Enter to cycle between Flow Switch 1, 2, 3, 4 and none. If the circulation pump turns off at night you
may not want this additional alarm output to be on which can be detected by no flow.
ManualTime 00:02:00
Day of Week smtwtfS
Off If Time < 22:00:00
Off If Time > 23:00:00
On Time
00:15:00
MinTimeOff
00:15:00
Off If ORP>700
Off If pH > 7.9
Off if Flow Off - 1
Superchlorination
Superchlorination
Use this relay control type to feed an increased amount of sanitizer once
a week or a couple times a week. This relay control type is the same as
the Feed Daily and only the new additional commands are discussed
here.
⧫
Manual Time 00:02:00
: The manual time can be used to test the
sanitizer feed for superchlorination to make sure it is connected
properly..
⧫
Day Of Week smtwtfs
: Set the days of the week to perform
superchlorination.
⧫
Off If Time < 00:00:00
: Set the time to start the superchlorination.
⧫
Off If Time > 00:00:00
: Set the time to end the superchlorination.
⧫
On Time 00:00:00 and MinTimeOff 00:00:00
: The mixing times may not be needed, but for a smaller
body of water you may want to feed sanitizer for 15 minutes and let it mix for another 15 with the relay
OFF to give the sanitizer time to mix.
⧫
Off If ORP>700:
The setpoint for a superchlorination cycle is to turn off if the ORP is higher than an ORP
setpoint. The feed cycle will continue until enough sanitizer has been added to reach this setpoint of the
Off If Time value has been reached. If you are going to feed a set amount of chlorine based on time only
set this value to 0 to skip it.
⧫
Off If pH> 7.9:
ORP is affected by pH and as the pH goes up the ORP value goes down. If when starting
the superchlorination cycle the acid storage tank is empty the pH may be at a higher then desired value
causing the ORP to be lower which could lead to feeding more sanitizer than desired. If you are going to
feed a set amount of chlorine based on time and not using the ORP setpoint then set this value to 0 to
skip it.
⧫
Off if Flow Off - 1
: The relay will be turned OFF if “No Flow” is detected in Flow Switch Input 1. Press
Enter to cycle between Flow Switch 1, 2, 3, 4 and none.
Water Level Control Type
Water Level is where an external pool water level feed can be connected to an Auxiliary Relay and
configured in this menu. If a water level switch is used it should be connected to Flow 2 for Pool1 and Flow 4
for Pool2. When the water is below the switch level then water should be added. The flow switch can be
either on when the water is low or off when the water is low depending on the type of switch, read the
following carefully to make sure you select the correct turn on condition.
⧫
Manual Time 00:02:00
: Is the amount of time you can set a relay to turn on manually (Default Setting 2
Minutes). To change the time, enter the new time and press
Enter
to save.
⧫
On if Flow On - none
: The Aux Water Level Relay will be turned on if “Flow” is detected in a Flow
Switch Input. Set this command to the appropriate flow switch input if the switch is ON when the water is
low. Note: If setting the On if Flow On to a switch value, leave On if Flow Off set to none.
⧫
On if Flow Off - none
: The Aux Water Level Relay will be turned on if “Flow” is detected in a Flow
Switch Input. Set this command to the appropriate flow switch input if the switch is OFF when the water
is low. Note: If setting the On if Flow Off to a switch value, leave On if Flow On set to none.