41
INTELLISTAT TS
TM
MONITOR OPERATION
ALARM MESSAGES AND DEFINITIONS
OPERATION CONTINUED
LOG / CURRENT / RS232
ALARM
BANNER
AC OUTPUT VOLTS X1-N HIGH = 121.3 THE OUTPUT VOLTAGE ON LINE 1 IS ABOVE
THE OUTPUT VOLTAGE HIGH SETPOINT.
TOTAL ALARM: 01
AC OUTPUT VOLTS X2-N HIGH = 121.3 THE OUTPUT VOLTAGE ON LINE 2 IS ABOVE
THE OUTPUT VOLTAGE HIGH SETPOINT.
TOTAL ALARM: 01
DC CHARGER FAIL
THE BATTERY CHARGER HAS FAILED.
TOTAL ALARM: 01
AC OUTPUT AMPS X1-N HIGH = 13.2
THE OUTPUT CURRENT ON LINE 1 IS ABOVE
THE OUTPUT CURRENT HIGH SETPOINT.
TOTAL ALARM: 01
AC OUTPUT AMPS X2-N HIGH = 13.2
THE OUTPUT CURRENT ON LINE 2 IS ABOVE
THE OUTPUT CURRENT HIGH SETPOINT.
TOTAL ALARM: 01
OUTPUT VA X1-N HIGH = 1200.2
THE OUTPUT VA ON LINE 1 IS ABOVE THE
OUTPUT VA HIGH SETPOINT.
TOTAL ALARM: 01
OUTPUT VA X2-N HIGH = 1200.2
THE OUTPUT VA ON LINE 2 IS ABOVE THE
OUTPUT VA HIGH SETPOINT.
TOTAL ALARM: 01
OUTPUT FREQUENCY HIGH = 66.2
THE OUTPUT FREQUENCY IS ABOVE 62.5 HZ.
TOTAL ALARM: 01
UNIT FAILED TO START
THE UNIT FAILED TO PROPERLY TURN ON.
UNIT FAILED TO START
BATTERY DC VOLTS HIGH = 155.2
THE BATTERY VOLTAGE IS ABOVE 150 VDC.
TOTAL ALARM: 01
BATTERY DC AMPS HIGH = 32.2
THE BATTERY CHARGING CURRENT IS ABOVE
THE CHARGING CURRENT HIGH SETPOINT.
TOTAL ALARM: 01
HIGH TOTAL OUTPUT VA = 2400.4
THE TOTAL VA IS ABOVE THE UNIT RATING.
TOTAL ALARM: 01
AC OUTPUT VOLTS X1-N LOW = 99.2
THE OUTPUT VOLTAGE ON LINE 1 IS BELOW
THE OUTPUT VOLTAGE LOW SETPOINT.
TOTAL ALARM: 01
AC OUTPUT VOLTS X2-N LOW = 99.2
THE OUTPUT VOLTAGE ON LINE 2 IS BELOW
THE OUTPUT VOLTAGE LOW SETPOINT.
TOTAL ALARM: 01
OUTPUT FREQUENCY LOW = 54.3
THE OUTPUT FREQUENCY IS BELOW 57.5 HZ.
TOTAL ALARM: 01
BATTERY DC VOLTS LOW = 113.2
THE BATTERY VOLTAGE IS BELOW THE
BATTERY VOLTAGE LOW SETPOINT.
TOTAL ALARM: 01
AC INPUT VOLTS L1-N HIGH = 134.2
THE INPUT VOLTAGE IS 9% ABOVE THE RATED
INPUT VOLTAGE.
TOTAL ALARM: 01
AC INPUT VOLTS L1-N LOW = 99.2
THE INPUT VOLTAGE IS 12% BELOW THE RATED
INPUT VOLTAGE.
TOTAL ALARM: 01
OUTPUT CIRCUIT BREAKER OPEN
OUTPUT CIRCUIT BREAKER HAS TRIPPED
TOTAL ALARM: 01
ON MANUAL BYPASS
SYSTEM IS ON MANUAL BYPASS.
ON MANUAL BYPASS
ON BATTERY 1.3 MIN
SYSTEM IS ON BATTERY
ON BATTERY 1.3 MIN
LAST POWER OFF: USER REPO
SYSTEM SHUTDOWN DUE TO USER REPO
TOTAL ALARM: 01
LAST POWER OFF:
OVERTEMPERATURE
SYSTEM SHUTDOWN DUE TO AN OVER
TEMPERATURE
TOTAL ALARM: 01
OVERTEMPERATURE WARNING
THERE IS AN OVER TEMPERATURE WARNING
TOTAL ALARM: 01
LAST POWER OFF: DC BUS VOLTAGE
HIGH
SYSTEM SHUTDOWN DUE TO AN
OVERVOLTAGE ON THE DC BUS.
TOTAL ALARM: 01
DC BUS VOLTAGE HIGH WARNING
THERE IS A DC BUS TOO HIGH WARNING.
TOTAL ALARM: 01
LAST POWER OFF: OVERLOAD
SYSTEM SHUTDOWN DUE TO AN OUTPUT
OVERLOAD.
TOTAL ALARM: 01
OVERLOAD WARNING
THERE IS AN OVERLOAD WARNING.
TOTAL ALARM: 01
LAST POWER OFF: DC BATTERY DC
VOLTS LOW
SYSTEM SHUTDOWN DUE TO A BATTERY CUT
OFF.
TOTAL ALARM: 01
BATTERY DC VOLTS LOW WARNING
BATTERY IS CLOSE TO CUT OFF.
TOTAL ALARM: 01
LAST POWER OFF: NORMAL
UNIT WAS SHUT OFF BY USER.
-
-
UNIT IS STARTING UP.
STARTING UP
-
ON BATTERY TEST.
BATTERY TST 00:11:35
-
THE SYSTEM IS ON MANUAL BYPASS AND
BATTERY.
ON MANL BYP & BTTRY
-
THE SYSTEM IS ON STATIC BYPASS.
ON STATIC BYPASS
-
THE SYSTEM IS NORMAL, NO ALARMS OR
CONDITIONS.
SYSTEM NORMAL
-
SYSTEM IS TURNED OFF.
CONTROL MODULE OFF