10
AC OUTPUT CURRENT MATRIX
PRELIMINARY INSTALLATION CONTINUED
4.5 KVA
5.5 KVA
6.5 KVA
7.5KVA
8.3 KVA
9.0 KVA
120V
37.5
45.8
----
----
----
----
220V
20.5
25
29.5
34.1
----
----
230V
19.6
23.9
28.3
32.6
----
----
120/208V
21.6
26.4
31.3
36.1
39.9
43.3
120/240V
18.8
22.9
27.1
31.3
34.6
37.5
120/208/240V
37.5 / 21.6 / 18.8
45.8 / 26.4 / 22.9
54.2 / 31.3 / 27.1
62.5 / 36.1 / 31.3
69.2 / 39.9 / 34.6
75.0 / 43.3 / 37.5
480V
9.4
11.5
13.5
15.6
17.3
18.8
10.0 KVA
11.0 KVA
12.0 KVA
13.5KVA
14.5 KVA
15.5 KVA
120V
----
----
----
----
----
----
220V
----
----
----
----
----
----
230V
----
----
----
----
----
----
120/208V
48.1
52.9
57.7
64.9
69.7
74.5
120/240V
41.7
45.8
50
56.3
60.4
64.6
120/208/240V
83.3 / 48.1 / 41.7
91.7 / 52.9 / 45.8
50.0 / 57.7 / 50.0
56.3 / 64.9 / 56.3
60.4 / 69.7 / 60.4
64.6 / 74.5 / 64.6
480V
20.8
22.9
25
28.1
30.2
32.3
OUTPUT
CURRENT
OUTPUT
CURRENT
OUTPUT
CURRENT
OUTPUT
CURRENT
OUTPUT
CURRENT
OUTPUT
CURRENT
OUTPUT
VOLTAGE
OUTPUT
VOLTAGE
OUTPUT MATRIX (KVA)
OUTPUT MATRIX (KVA)
OUTPUT
CURRENT
OUTPUT
CURRENT
OUTPUT
CURRENT
OUTPUT
CURRENT
OUTPUT
CURRENT
OUTPUT
CURRENT
When output breaker options are not purchased, overcurrent protection and disconnection means shall be provided by others.
Based on breaker size and derating factor of 0.88 per NEC Table 310.16. The wire bending space on the “S” cabinet is 2” (i.e. maxi-
mum conductor of 3 AWG) and on the “T” cabinet is 7” (maximum conductor of 500 kcmil allowed – the terminal supports up to 2/0).
This unit is intended for installation in a temperature controlled, indoor area free of conductive contaminants.
Per the NEC, Table 310.16, for a 40
°
C ambient, the wire sizes are as follows:
Without Distribution:
Cabinet S - 4 AWG
Cabinet T - 1 AWG
With Distribution
(for all cabinets):
100A - 2 AWG
90A - 2 AWG
80A - 3 AWG
70A - 4 AWG
60A - 4 AWG
50A - 6 AWG
40A - 8 AWG
30A - 10 AWG
20A - 12 AWG
15A - N/A
AC OUTPUT WIRE SIZING