23
COMMUNICATIONS DESCRIPTION
ALARM TERMINAL DESCRIPTION
FOR 125VAC DISCREET WIRING SCENARIOS
Eleven (11) position contact closure terminal. Provides R.E.P.O., Test Active, General Alarm, Low Battery and On
Battery. Note: User selectable, Normally open or closed, Dry contacts rated: 125VAC @ 0.5 Amps.
REAR VIEW OF INVERTER CABINET
K6
SW1 DIP SWITCHES
2
USB PORT (FOR SERVICE
USE ONLY)
3
NETMINDER ETHERNET PORT
4
RS232 PORT (NOT USED)
5
AUX. PORT (NOT USED)
6
1
1
2
3
4
5
6
2
3
4
5
6
“S” CABINET
“T” CABINET
1 K6 ALARM TERMINAL
1
*CONT
ACTS
ARE USER SELECT
ABLE NORMALL
Y OPEN OR NORMALL
Y CLOSED BY
MEANS
OF JUMPERS ON CONTROL
BOARD LOCA
TED JUST
BELOW
THE
TERMINALS
AS SHOWN
ABOVE.
THESE JUMPERS CAN BE
ACCESSED BEHIND INNER DOOR, BEHIND CONTROL
MODULE CLOSEOUT
P
ANEL, ON
THE CONTROL
BOARD.
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
J9
J10
J8
J7
Customer supplied, Normally Open, Dry Contact Input
R.E.P.O.
TEST ACTIVE
LOW BATTERY
ON BATTERY
GENERAL ALARM
+5.5VDC
COMMON
(Normally Open, Dry Contact Output*)
(Normally Open, Dry Contact Output*)
(Normally Open, Dry Contact Output*)
(Normally Open, Dry Contact Output*)
CHASSIS GROUND
(Normally Open,
Dry Contact Output*)
(Normally Open,
Dry Contact Output*)
(Normally Open,
Dry Contact Output*)
(Normally Open,
Dry Contact Output*)
“S” CABINET
TERMINAL ORIENTATION
R.E.P.O.
TEST ACTIVE
LOW BATTERY
ON BATTERY
GENERAL ALARM
+5.5VDC
COMMON
CHASSIS
GROUND
Customer supplied,
Normally Open,
Dry Contact Input
*CONTACTS ARE USER SELECTABLE NORMALLY OPEN OR NORMALLY CLOSED BY MEANS
OF JUMPERS ON CONTROL BOARD LOCATED JUST BELOW THE TERMINALS AS SHOWN
ABOVE. THESE JUMPERS CAN BE ACCESSED BEHIND INNER DOOR, BEHIND CONTROL
MODULE CLOSEOUT PANEL, ON THE CONTROL BOARD.
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
J9
J10
J8
J7
K6
1
“T” CABINET
TERMINAL ORIENTATION