39
INTELLISTAT TS
TM
MONITOR OPERATION
ANNUAL BATTERY TESTING
Default customer password = 05151
OPERATION CONTINUED
SYSTEM NORMAL
TIME: 07:58:00 AM
DATE: 04/16/10
ANNUAL BATTERY TEST SETPOINTS
EXIT
PERIOD
MANUAL
ANNUAL
FACTORY
TEST
DISABLED. PUSH TO ENABLE.
ANNUAL TEST DURATION : 60 SEC
TIME & DATE : 09:49 PM 04/21/11
TIME: 07:58:17 AM
DATE: 04/16/10
ANNUAL BATTERY TEST SETPOINTS
EXIT
PERIOD
MANUAL
ANNUAL
FACTORY
BATTERY TST 00:00:10
TESTING
DISABLED. PUSH TO ENABLE.
ANNUAL TEST DURATION : 60 SEC
TIME & DATE : 09:49 PM 04/21/11
TIME: 07:58:20 AM
DATE: 04/16/10
ANNUAL BATTERY TEST SETPOINTS
EXIT
PERIOD
MANUAL
ANNUAL
FACTORY
BATTERY TST 00:00:07
ABORT
DISABLED. PUSH TO ENABLE.
ANNUAL TEST DURATION : 60 SEC
TIME & DATE : 09:49 PM 04/21/11
Push to enable the
test on a yearly basis.
Factory preset disabled.
The test will auto run
at the time and date
programmed. Factory
preset to the 15th of
the following month,
one year from date of
shipment at 10PM.
Time and Date are user
accessible.
The timer will count
down until the test is
complete and then
terminate the test
automatically. Test
results can be found
in the “TST LOG”
Menu.
While testing the
button will change
from “TESTING” to
“ABORT”. Press
the “ABORT” button
should you want
to terminate the
test immediately.
T h e b u t t o n w i l l
t h e n c h a n g e t o
“ABORTING” then
again back to the
original green “TEST”
button.
Test results can be found
in the “TST LOG” Menu.
If the “TST LOG” register
is full the system will
delete the oldest entry
to make room for the
new entry automatically.
Aborting the test will
result in a “Annual Test :
Incomplete” entry in the
TST LOG.
Pushing the test button will invoke the test regardless if the enable/disabled button is enabled or not.
Press the “TEST”
button to invoke a
battery test
(Duration
= 60 seconds). The
duration is preset at the
factory and is not user
accessible. Contact
the factory should the
duration time need to
be modified.
NOTE :
Invoking a test
by pressing the “TEST”
button will automatically
change the date and time
of the Annual Test to the
date and time that the
test button is pushed. The
auto test will commence
exactly one year later on
the same date and time
the test button was initially
pushed (if enabled).