Dinverter
A
User Guide
Issue code: d2au9
84
8
Diagnostics
Warning
The Drive contains hazardous electrically live parts. Do not
attempt to repair a defective Drive. Return the Drive to a
Control Techiques Drive Centre or distributor for repair
8.1 Status
messages
When in Status mode, the display shows one of the following status
messages:
Display
Status
Conditions
rdY
The Drive is ready to receive a
start
command, but is not
applying power to the motor.
A
DRIVE ENABLE
signal is applied to terminal B4
(connected to 0V common).
An
External trip
signal is not present
(B5 connected to 0V common).
inh
The Drive is disabled, and is not
applying power to the motor. If
the motor is already running, it
will coast to rest.
The
DRIVE ENABLE
signal has been removed from
terminal B4.
dEC
The Drive is decelerating the
motor to rest.
A
stop
command has been received.
dc
DC injection braking current is
being applied by the Drive to the
motor.
A
stop
command has been received and
0.16
Stop
mode selector
is set at
rP.I
or
dcI
.
trP
The Drive has tripped, and is not
applying power to the motor.
See
Changing a parameter value after a trip occurs
later in this chapter.
[Value]
The Drive is running.
The value displayed relates to the initial parameter
selected by parameter
0.38
or the parameter last
selected by the user. The initial parameter
displayed by default is
0.10
Motor frequency
.