Commander SE User Guide
44
Issue Number 5
L1 - Level 1 access - Only parameters 1 to 10 can be selected for viewing or adjusting.
L2 - Level 2 access - All parameters 1 to 44 can be selected for viewing or adjusting.
Loc - Used to lock a security code in the Drive. See Security codes in Section 6.5.
6.10.3Level 2 parameters
Defines the preset speed 1.
For setting of negative preset speed values, see parameter 17.
Defines the preset speed 2.
For setting of negative preset speed values, see parameter 17.
Defines the preset speed 3.
For setting of negative preset speed values, see parameter 17.
Defines the preset speed 4.
For setting of negative preset speed values, see parameter 17.
Defines the jog speed.
Defines the current input on Analog input reference 2, terminal 5. Definition of the
current input mode is given in the following sub-table:
No.
Function
Type
Limitations
Range
Units
Defaults
10
Parameter
access
RW
T
L1, L2, Loc
L1
EUR
L1
USA
No.
Function
Type
Limitations
Range
Units
Defaults
11
Preset 1
RW
B
±1000.0
Hz
0.0
EUR
0.0
USA
No.
Function
Type
Limitations
Range
Units
Defaults
12
Preset 2
RW
B
±1000.0
Hz
0.0
EUR
0.0
USA
No.
Function
Type
Limitations
Range
Units
Defaults
13
Preset 3
RW
B
±1000.0
Hz
0.0
EUR
0.0
USA
No.
Function
Type
Limitations
Range
Units
Defaults
14
Preset 4
RW
B
±1000.0
Hz
0.0
EUR
0.0
USA
No.
Function
Type
Limitations
Range
Units
Defaults
15
Jog
reference
RW
U
0 - 400.0
Hz
1.5
EUR
1.5
USA
No.
Function
Type
Limitations
Range
Units
Defaults
16
Current
input
mode
RW
T
0-20, 20-0
4-20, 20-4
4-.20, 20-.4
mA
4-.20
EUR
4-.20
USA
Mode
Description
0 - 20
Current input 0 to 20mA (20mA full scale)
20 - 0
Current input 20mA to 0mA (0mA full scale)
4 - 20
Current input 4mA to 20mA with current loop loss (cL) trip (20mA full scale)
20 - 4
Current input 20mA to 4mA with current loop loss (cL) trip (4mA full scale)
4 - .20
Current input 4mA to 20mA with no current loop loss (cL) trip (20mA full scale)
20 - .4
Current input 20mA to 4mA with no current loop loss (cL) trip (4mA full scale)