Table 3.3 Commander SE Size 2, 200V dual rated units
* See section 3.1.1.
** For an explanation of inrush current, see section 3.1.2.
Table 3.4 Recommended supply fuses and cables
Table 3.5 Braking resistors
Before fitting a braking resistor please read the information on Braking, and
the Warnings on High Temperatures and Overload Protection at the end of
this section.
MODEL
SE2D200...
075
110
150
220
AC supply voltage and frequency
Single or 3 phase 200 to 240V +/- 10%, 48 to 62Hz
Input displacement factor (cos
φ
)
>0.97
Nominal motor power - kW
0.75
1.1
1.5
2.2
Nominal motor power - HP
1.0
2.0
3.0
Output voltage and frequency
3 phase, 0 to input voltage, 0 to 1000Hz
100% RMS output current - A
4.3
5.8
7.5
10.0
150% overload current for 60 secs - A
6.5
8.7
11.3
15.9
Typical full load input current - A* 1ph/3ph
11.0
5.5
15.1
7.9
19.3
9.6
26.2
13.1
Typical inrush current - A**(duration <10ms)
55
35
Drive power losses at 230VAC at 6kHz switching
frequency - W
54
69
88
125
Weight - kg/lb
2.75 / 6
Cooling fan fitted
No
Yes
MODEL
SE2D200...
075
110
150
220
1ph
3ph
1ph
3ph
1ph
3ph
1ph
3ph
Recommended input supply fuse - A
16
10
20
16
25
16
32
20
Control cable
mm²
≥
0.5
AWG
20
Recommended input cable
mm²
1.5
1.0
2.5
1.5
2.5
1.5
4.0
2.5
AWG
14
16
12
14
12
14
10
12
Recommended motor cable
mm²
1.0
1.5
AWG
16
14
Recommended braking resistor cable
mm²
1.0
1.5
AWG
16
14
MODEL
SE2D200...
075
110
150
220
Minimum braking resistor value -
Ω
50
40
Recommended braking resistor value -
Ω
100
75
50
Maximum braking current - A
9
11
Resistor peak power rating - kW
1.8
2.4
3.5
NOTE