Commander SE User Guide
6
Issue Number 5
3
Technical Data
3.1
Power dependant rating data
Model code explanation
SE1 - frame size 1, SE2 - frame size 2, SE3 - frame size 3,
SE4 - frame size 4.
1 - single phase, D - Dual rating (single and three phase), 3 - three phase
2 - 230VAC nominal input voltage, 4 - 400VAC nominal input voltage
00 - for expansion of Drive power range
025 to 1500 - 0.25 kW to 15 kW output power
Table 3.1 Commander SE Size 1
* See section 3.1.1.
** For an explanation of inrush current, see section 3.1.2.
Table 3.2 Recommended supply fuses and cables
MODEL
SE11200...
025
037
055
075
AC supply voltage and frequency
Single phase 200 - 240V +/- 10% 48 - 62Hz
Input displacement factor (cos
φ
)
>0.97
Nominal motor power - kW
0.25
0.37
0.55
0.75
Nominal motor power - HP
0.50
1.0
Output voltage and frequency
3 phase, 0 to input voltage, 0 to 1000Hz
100% RMS output current - A
1.5
2.3
3.1
4.3
150% overload current for 60 secs - A
2.3
3.5
4.7
6.5
Typical full load input current - A*
5.6
6.5
8.8
11.4
Typical inrush current - A** (duration <10ms)
100
Drive power losses at 230VAC at 6kHz switching
frequency - W
18
24
37
56
Weight - kg/lb
1.1/2.4
1.25/2.75
Cooling fan fitted
No
MODEL
SE11200...
025
037
055
075
Recommended input supply fuse - A
6
10
16
Control cable
mm²
≥
0.5
AWG
20
Recommended input cable
mm²
1.0
1.5
AWG
16
14
Recommended motor cable
mm²
1.0
AWG
16