Commander SE User Guide
Issue Number 5
29
Further data for the filters is given in the following tables:
Table 4.11 Commander SE Size 1
Table 4.12 Commander SE Size 2
Table 4.13 Commander SE Size 3
*Also used on Size 2 units.
Table 4.14 Commander SE Size 4
For tables 4.11 to 4.14, please be aware of the following:
Weight is unpacked weight.
Worst case leakage current:
Single phase filters - when the neutral is disconnected.
Three phase filters - when an input phase is disconnected.
The data is given for an input voltage of 230V, 50Hz.
Part Number
Maximum
Power
Losses
IP Rating
Weight
kg
Operational
Leakage
Current
mA
Worst Case
Leakage
Current
mA
4200-6101
6
21
0.49
4.0
8.0
4200-6102
6
20
0.60
40.7
77.5
4200-6103
6
21
0.60
2.9
5.7
Part Number
Maximum
Power
Losses
IP Rating
Weight
kg
Operational
Leakage
Current
mA
Worst Case
Leakage
Current
mA
4200-6201
10.1
20
1.2
89
128
4200-6202
10.1
20
1.1
45.7
184.2
4200-6203
15.4
20
1.3
26.4
106.3
4200-6204
6
20
0.7
29.5
58.9
4200-6205
10.1
20
1.2
2.8
5.7
4200-6207
10.1
20
1.1
3
18.3
4200-6209
15.4
20
1.3
2.6
15.5
Part Number
Maximum
Power
Losses
IP Rating
Weight
kg
Operational
Leakage
Current
mA
Worst Case
Leakage
Current
mA
4200-6301
12.4
20
1.6
45.7
184.2
4200-6302
19.5
20
1.7
26.4
106.3
4200-6303
*
10.8
20
0.8
14.1
68
4200-6304
*
6.1
20
0.6
33
148
Part Number
Maximum
Power
Losses
IP Rating
Weight
kg
Operational
Leakage
Current
mA
Worst Case
Leakage
Current
mA
4200-6401
26.1
20
3.1
29.4
280
4200-6402
11.7
20
1.1
14.1
68
NOTE