Power supply and control connections to the SPM Power Selector Module are shown in
Figure 4-2 and Table 4-1 below.
Figure 4-2 Control connections
Table 4-1 Terminal connections
The external 24Vdc supply to the SPM Power Selector Module must be provided with
either a 3A fuse or other over-current protection device as specified in section
7.3
WARNING
Provide a fuse or other over-current protection device in the contactor relay circuit with
a rating not greater than that specified in section 7.3
WARNING
Do not attempt to carry out internal repairs. Return faulty units to the supplier for repair.
WARNING
Contactor
terminal
Function
Control
Function
1
Contactor 1+2 power supply
1
+ 24 Vdc
2
Contactor output 1
2
0 Volt
3
Contactor 1+2 power supply
3
Digital output
4
Contactor output 2
4
24V Master Mode Select
5
Contactor 3+4 power supply
5
Master Mode Select
6
Contactor output 3
7
Contactor 3+4 power supply
8
Contactor output 4