Parameters table

 

Below are listed all the programming parameters. For each parameter are indicated the setting range, the factory default, as well as a description of the function.

 

 

GENERAL menu

 

 

PASSWORD

 

UoM

 

Default

 

Range

 

1

 

Level 1 (viewing) 

0 (OFF)-999999999 

2

 

Level 2 (setup) 

0 (OFF)-999999999 

3

 

Key enabling  

min 

1-60 

4

 

Key lock 

NO 

YES-NO 

5

 

Communication lock 

NO 

YES-NO 

6

 

Enable options 

0 (OFF)-999999999 

NOTE: Password Recovery. If you forget your password, contact Technical Support. 
1

 - When the password is defined, value to be specified to allow the user to scroll the pages.

 

2

 - When the password is defined, value to be specified to get user configuration access. 

3

 - Setting the minutes for which the password enables the protected functions. 

4

 - If set to YES, the password protects the use of the keys. Enter numeric code to unlock the keys. 

5

 - If set to YES, the password protects the communication setup messages on the serial or TCP bus.

 

6

 - Numeric code that unlock firmware functions.

 

 

RESET

 

Range

 

1

 

Global 

All device parameters are resetted to factory default value. 

2

 

Setup to default 

All setup parameters are resetted to factory default value. 

3

 

All energies 

Clears total and tariff energy meters. 

4

 

TB energies 

Clears tariff energy meters. 

5

 

Counters 

Clears counters. 

6

 

TB counters 

Clears tariff counters. 

MIN-MAX 

Reset of MAX and MIN peaks of all readings. 

Max Demand 

Reset of Max Demand of all readings. 

Energy graphs 

Clears the energy graphics. 

10 

Log setpoint 

Clears the alarm log events. 

11 

All log 

Clears the log memory (both events and measurements log). 

12 

ON / OFF events 

Clears the power supply switch ON/OFF events.  

13 

Setpoint DO 

Manual command in order to reset the digital output of the alarm setpoint. 

14 

DIP / SWELL 

Clears the DIP / SWELL log memory. 

 

DATE AND TIME

 

 

 

 

- The EMA-D6 manages the date and time, that is used for the storage events and for time-related functions. The EMA-D6 is equipped with a module with RTC 
(real-time clock), then the time and date are kept updated even without auxiliary power supply, for a maximum of about 1 week. 
 

UTILITY

 

Default

 

Range

 

1

 

Language 

English 

English 
Italiano 

Deutsche 

Francais 
Svenska 

Espanol 

2

 

Theme 

Blue-Black 

Blue-Black

White 

Red-Black

White 

Yellow-Black

White 

Grey-Black

White 

3

 

Font dimension 

Standard 

Standard-Big 

4

 

Set-point alert 

OFF 

ON-OFF-First Out  

5

 

Protocol 

Standard 

Standard-(old EMA devices) 

4

 - When it is activated the display page switches automatically on the alarm page, and the alarm is shown with the Warning icon.

 

5

 - When it is selected the old devices, the communication protocol switches on the old EMA-90. 

 

DISPLAY

 

UoM

 

Default

 

Range

 

1

 

Brightness 

15 

1-15 

2

 

Default page return 

NO 

NO-YES 

3

 

Stand-by 

YES 

NO-YES 

4

 

Stand-by time 

min 

10 

1-60 

5

 

Refresh 

ms 

1-60 

1

 - Set up the level of brightness display. 

2

 - If set to NO the display will remains in the page where the user left it. If set to a time delay, after that time the display page goes back to page set as default. 

4

 - Set up the time after that the display will switch off. The lifetime of the graphical display depends on its brightness and stand-by time. It is highly recommended to 

limit the brightness level of the display in order to ensure a longer lifetime of the device. 

5

 - Display update time. 

Note: 1 = 250 ms

 

Содержание EMA-D6

Страница 1: ...pag 1 22 INSTRUCTION MANUAL IM114 U v0 2 EMA D6 DIN rail network analyzer with basic power quality analysis...

Страница 2: ...rated via the front of the device to guard against unauthorized access Description Modular DIN rail housing 6 modules Backlighted LCD display True RMS measurements For current transformers x 1 A and x...

Страница 3: ...ase refer to section Measure menu Transform ratio 6 Set the date and time on the device please refer to section General menu Date Time Access to device The network analyzer features a front panel with...

Страница 4: ...gs to enter configuration mode press and keys Select the required sub menu with keys and confirm with To exit setup and go back to the readings viewing press The following table show the available sub...

Страница 5: ...atically scaled in order to fit the waveforms on the screen The graph is automatically updated every refresh time selected by the user DISPLAY menu Every page shows the total harmonic distortion THD a...

Страница 6: ...anages the date and time that is used for storage of events for measurements log and for time related functionalities The EMA D6 is equipped with RTC real time clock then the time and date are kept up...

Страница 7: ...s programming and definition refer to setup menu SETPOINT chapter For more information on how the meter handles the setpoint driven alarms refer to the figure below Data logger function The data logge...

Страница 8: ...oint Log Logic expression Password Reset Date Time Utility Display Graphics Editing contacts Transform ratio Time window Frequency DIP SWELL Wiring Convention Type Modality Energy Counter Ethernet LAN...

Страница 9: ...the log memory both events and measurements log 12 ON OFF events Clears the power supply switch ON OFF events 13 Setpoint DO Manual command in order to reset the digital output of the alarm setpoint...

Страница 10: ...V 205000 10000 2000000000 6 Interruption hysteresis mV 275000 10000 2000000000 7 Storage End memory FIFO End memory 1 Threshold active when the voltage is lower than value set 2 The duration of voltag...

Страница 11: ...d capacitive apparent energy 6 10 Set a value of energy meters L2 for active energy imported and exported reactive energy inductive and capacitive apparent energy 11 15 Set a value of energy meters L3...

Страница 12: ...16 daily plans HOLIDAY n n 1 48 UoM Default Range 1 Month holiday January January December 2 Day holiday 1 1 31 3 Plan holiday Daily plan 1 Daily plan 1 16 NOTE HOLIDAY menu supports a maximum of 48...

Страница 13: ...when EMA D6 will be configured as Slave ETHERNET optional UoM Default Range 1 IP Address 10 0 0 100 000 000 000 000 255 255 255 255 2 Subnet mask 255 0 0 0 000 000 000 000 255 255 255 255 3 IP gateway...

Страница 14: ...ulse counter is divided by this coefficient 4 Status on activation of the input Allows reversing the logic of the input function 5 When digital input is using as SP DO reset select the number of setpo...

Страница 15: ...t be compared with limits 5 Used to define the upper threshold 6 Used to define the unit of measure of the upper threshold 7 Used to define the lower threshold 8 Used to define the unit of measure of...

Страница 16: ...e memory is full you can choose to stop the recording End Memory mode or to continue overwriting the oldest records FIFO mode 4 5 6 7 Set the variables driven by date range or and time interval that c...

Страница 17: ...gies Digital inputs Counters Analog input Math 11 Item 2 OFF measures 12 Multiplier 2 1 1 100000 13 Divisor 2 1 1 100000 NOTE this menu is divided into 8 sections for logic expression LE1 8 1 Expressi...

Страница 18: ...neutral voltage VL3 23 A signal COM2 RS 485 optional 6 Phase current IL3 output S2 15 Not used 24 B signal COM2 RS 485 optional 7 Neutral current IN input S1 optional 16 Neutral conductor VN 25 A sign...

Страница 19: ...e phase measuring two conductors without voltage transformers 6 Three phase measuring four conductors balanced multiple loads with one current transformer with three current transformers Connection ty...

Страница 20: ...ransformer Connection type 3X1PH Digital outputs connection L Load F Fuse V 12 250 VAC 150 mA max 10 300 VDC 150 mA max Digital inputs connection Input voltage 24 or 48 or 115 or 230 VAC DC to be defi...

Страница 21: ...ce ph n 1 65 Mohms Power consumption per phase 0 09VA AC current inputs Rated current 1 A or 5 A Measuring range For 1 A scale 10 mA 1 A For 5 A scale 50 mA 5 A Type of input Isolated inputs by intern...

Страница 22: ...5 Ethernet 10BASE T or 100BASE TX auto sensing Connector type RJ45 Protocol supported Modbus TCP Connections Type of terminal Screw fixed Number of terminals 36 Conductor cross section 0 2 2 5 mm2 Tig...

Отзывы: