WARNING!

 

 

Carefully read the manual before the installation or use.

 

 

This device is to be installed by qualified personnel, complying to current standards, to avoid damages.

 

 

Before any maintenance operation on the device, remove supply inputs.

 

 

The manufacturer cannot be held responsible for electrical safety in case of improper use of the equipment.

 

 

Products illustrated herein are subject to alteration and changes without

 

prior notice.

 

 

Introduction

 

The EMA-D6 is a Network Analyzer for displaying all the relevant system parameters in low and medium voltage power distribution. It is capable of single-phase, 
two-phase or three-phase measurement and can be used in two-wire, three-wire, four-wire, TN, TT and IT systems. 

 

Thanks to its large measured voltage range, the EMA-D6 with multi-range power supply can be connected in any low and medium voltage system up to a rated 
system voltage of 690 VAC.

 

Higher voltages can be measured using voltage transformers. For measuring current, either x/1 A or x/5 A current transformer can be used or Rogowski coil 
(optional), TT/TTA sensors (optional) or 333 mV (optional).

 

The combination of four function keys with the multi-language plaintext displays makes intuitive user prompting possible. The graphic color LCD offers user-friendly 
interface.

 

The RS-485 or Ethernet interface or an optionally available interface module can be used for communication. In addition, the EMA-D6 has a multifunctional digital 
output using an alarm. The analyzer can accept up to 4 digital inputs. The parameters can be set either direct on the device or via the communications interface. 
Password protection is integrated via the front of the device to guard against unauthorized access.

 

 

Description

 

 

Modular DIN-rail housing, 6 modules

 

 

Backlighted LCD display

 

 

True RMS measurements

 

 

For current transformers x/1 A and x/5 A, Rogowski coil (optional), TT/TTA sensors (optional), 333 mV (optional)

 

 

Keyboard with 4 keys for viewing and setting

 

 

Easy and fast navigation

 

 

Derivation of more than 50 measured variables from the basic measured variables with maximum, minimum, average and max demand values

 

 

Continuous sampling (128 @ waveform)

 

 

High measuring accuracy 

 

 

Harmonics V, I up to 63th order (optional)

 

 

Up to 4 digital outputs

 

 

Up to 4 digital inputs

 

 

Up to 2 RS-485 communication (Modbus RTU protocol) (COM2 optional)

 

 

ETHERNET interface (Modbus TCP protocol) (optional)

 

 

Voltage measurement

 

- Direct measurement on the system or using voltage transformers. External voltage transformers are required to measure higher voltages than the permissible 

 

rated input voltages.

 

- Measuring voltage to 400 VAC / 690 VAC with multi-range power supply. The device is designed for measuring input voltages up to 400 VAC to the neutral 
conductor and 690 VAC to Vph-ph.

 

 

Current measurement

 

- Measuring current of 1 A or 5 A for connecting standard current transformers. Rogowski coil (optional), TT/TTA sensors (optional).

 

 

Neutral or differential measurement

 

- The fourth current  input channel (I4) is used to measure the current on the neutral line or differential current.

 

- If the CT for the neutral wire is not available, the measure of I4 input will be calculated from the phase currents.

 

 

LED and keyboard functions

 

 

Display 

LED ON: presence of auxiliary supply 

Communication traffic LED 

Energy pulsing LED 

LED used for notifications (alarms, warnings, errors) 

Cancellation or navigation key among the visualization pages 

Up 

Down 

Confirmation or navigation key among the visualization pages 

 
   
                                         
 

 
 
 

 
 

 

Содержание EMA-D6

Страница 1: ...pag 1 22 INSTRUCTION MANUAL IM114 U v0 2 EMA D6 DIN rail network analyzer with basic power quality analysis...

Страница 2: ...rated via the front of the device to guard against unauthorized access Description Modular DIN rail housing 6 modules Backlighted LCD display True RMS measurements For current transformers x 1 A and x...

Страница 3: ...ase refer to section Measure menu Transform ratio 6 Set the date and time on the device please refer to section General menu Date Time Access to device The network analyzer features a front panel with...

Страница 4: ...gs to enter configuration mode press and keys Select the required sub menu with keys and confirm with To exit setup and go back to the readings viewing press The following table show the available sub...

Страница 5: ...atically scaled in order to fit the waveforms on the screen The graph is automatically updated every refresh time selected by the user DISPLAY menu Every page shows the total harmonic distortion THD a...

Страница 6: ...anages the date and time that is used for storage of events for measurements log and for time related functionalities The EMA D6 is equipped with RTC real time clock then the time and date are kept up...

Страница 7: ...s programming and definition refer to setup menu SETPOINT chapter For more information on how the meter handles the setpoint driven alarms refer to the figure below Data logger function The data logge...

Страница 8: ...oint Log Logic expression Password Reset Date Time Utility Display Graphics Editing contacts Transform ratio Time window Frequency DIP SWELL Wiring Convention Type Modality Energy Counter Ethernet LAN...

Страница 9: ...the log memory both events and measurements log 12 ON OFF events Clears the power supply switch ON OFF events 13 Setpoint DO Manual command in order to reset the digital output of the alarm setpoint...

Страница 10: ...V 205000 10000 2000000000 6 Interruption hysteresis mV 275000 10000 2000000000 7 Storage End memory FIFO End memory 1 Threshold active when the voltage is lower than value set 2 The duration of voltag...

Страница 11: ...d capacitive apparent energy 6 10 Set a value of energy meters L2 for active energy imported and exported reactive energy inductive and capacitive apparent energy 11 15 Set a value of energy meters L3...

Страница 12: ...16 daily plans HOLIDAY n n 1 48 UoM Default Range 1 Month holiday January January December 2 Day holiday 1 1 31 3 Plan holiday Daily plan 1 Daily plan 1 16 NOTE HOLIDAY menu supports a maximum of 48...

Страница 13: ...when EMA D6 will be configured as Slave ETHERNET optional UoM Default Range 1 IP Address 10 0 0 100 000 000 000 000 255 255 255 255 2 Subnet mask 255 0 0 0 000 000 000 000 255 255 255 255 3 IP gateway...

Страница 14: ...ulse counter is divided by this coefficient 4 Status on activation of the input Allows reversing the logic of the input function 5 When digital input is using as SP DO reset select the number of setpo...

Страница 15: ...t be compared with limits 5 Used to define the upper threshold 6 Used to define the unit of measure of the upper threshold 7 Used to define the lower threshold 8 Used to define the unit of measure of...

Страница 16: ...e memory is full you can choose to stop the recording End Memory mode or to continue overwriting the oldest records FIFO mode 4 5 6 7 Set the variables driven by date range or and time interval that c...

Страница 17: ...gies Digital inputs Counters Analog input Math 11 Item 2 OFF measures 12 Multiplier 2 1 1 100000 13 Divisor 2 1 1 100000 NOTE this menu is divided into 8 sections for logic expression LE1 8 1 Expressi...

Страница 18: ...neutral voltage VL3 23 A signal COM2 RS 485 optional 6 Phase current IL3 output S2 15 Not used 24 B signal COM2 RS 485 optional 7 Neutral current IN input S1 optional 16 Neutral conductor VN 25 A sign...

Страница 19: ...e phase measuring two conductors without voltage transformers 6 Three phase measuring four conductors balanced multiple loads with one current transformer with three current transformers Connection ty...

Страница 20: ...ransformer Connection type 3X1PH Digital outputs connection L Load F Fuse V 12 250 VAC 150 mA max 10 300 VDC 150 mA max Digital inputs connection Input voltage 24 or 48 or 115 or 230 VAC DC to be defi...

Страница 21: ...ce ph n 1 65 Mohms Power consumption per phase 0 09VA AC current inputs Rated current 1 A or 5 A Measuring range For 1 A scale 10 mA 1 A For 5 A scale 50 mA 5 A Type of input Isolated inputs by intern...

Страница 22: ...5 Ethernet 10BASE T or 100BASE TX auto sensing Connector type RJ45 Protocol supported Modbus TCP Connections Type of terminal Screw fixed Number of terminals 36 Conductor cross section 0 2 2 5 mm2 Tig...

Отзывы: