MEASURE menu 

 

TRANSFORM RATIO

 

UoM

 

Default

 

Range

 

1

 

CT primary 

1-400000 

2

 

CT secondary 

1-400000 

3

 

CT N primary 

1-400000 

4

 

CT N secondary 

1-400000 

5

 

VT primary 

1-400000 

6

 

VT secondary 

1-400000 

Note: If Rogowski coils are used, it is not needed to set any transformation ratio. 
1

 - CT primary winding rated current.

 

2

 - CT secondary winding rated current.

 

3

 - CT Neutral primary winding rated current.

 

4

 - CT Neutral secondary winding rated current.

 

5

 - VT primary winding rated current.

 

6

 - VT secondary winding rated current. 

 

INTEGRATION

 

UoM

 

Default

 

Range

 

1

 

Time interval 

min 

15 

1-2-3-5-6-10-12-15-20-30-60 

2

 

Type 

Shifting 

Shifting-Fixed 

1

 - Selection the integration time interval.

 

2

 - Selection of average reading calculation mode: 

Shifting

 = The instantaneous values are integrated for a period.  

Fixed

 = Readings are integrated for a fixed rated. Every time the integration time elapses, the average value is updated with the result of the last integration.

 

 

FREQUENCY

 

UoM

 

Default

 

Range

 

1

 

Fundamental 

Hz 

50 

50-60 

1

 - Rated frequency of the line. Possible nominal frequency values: 50 Hz or 60 Hz. 

 

DIP / SWELL

 

UoM

 

Default

 

Range

 

1

 

DIP threshold 

mV 

190000 

10-10000000 

DIP cycles 

cycles 

250 

1-10000 

SWELL threshold 

mV 

270000 

10-10000000 

SWELL cycles 

cycles 

250 

1-10000 

Interruption threshold 

mV 

205000 

10000-2000000000 

Interruption hysteresis 

mV 

275000 

10000-2000000000 

Storage 

End memory 

FIFO 

End memory

 

1

 - Threshold active when the voltage is lower than value set.

 

2

 - The duration of voltage dip. 

Note: 1 = 20 ms

 

3

 - Threshold active when the voltage is higher than value set.

 

4

 - The duration of swell over-voltages. 

Note: 1 = 20 ms

 

5

 - Voltage interruption begins when the RMS value falls below this threshold. A voltage interruption ends when the voltage is equal to, or greater than, interruption 

threshold plus the hysteresis. 

6

 - Hysteresis delay on voltage interruption. 

7

 - When the memory is full, the user can choose to stop the recording (end memory) or to continue overwriting the oldest records (FIFO). 

 

WIRING / CONVENTION

 

UoM

 

Default

 

Range

 

1

 

Wiring 

3 phase (4 or 3 wires) 

3 phase (4 or 3 wires) 

ARON 

3 phase balanced 

3 phase multiload balanced 

Single phase 

Single phase multiload 

Triple single phase 

Two-phase (3 wires) 

4th input current 

Measured 

Computed-Measured 

Differential-Differential filter 

PF convention 

SIGN 

SIGN-IEC-IEEE 

Setpoint timing 

0.1 or 1 

1

 - Set this parameter according to the used wiring diagram. See wiring diagrams section on the manual.

 

2

 - The fourth current input channel (I4) is used to measure the current on the neutral line or differential current. If the CT for the neutral wire is not available, the I4 

input can be calculated from the phase currents.  

 

3

 - The meter shows positive or negative power factor according to selected standard.

 

4

 - Set the setpoint intervention time.

 

 
 
 

Содержание EMA-D6

Страница 1: ...pag 1 22 INSTRUCTION MANUAL IM114 U v0 2 EMA D6 DIN rail network analyzer with basic power quality analysis...

Страница 2: ...rated via the front of the device to guard against unauthorized access Description Modular DIN rail housing 6 modules Backlighted LCD display True RMS measurements For current transformers x 1 A and x...

Страница 3: ...ase refer to section Measure menu Transform ratio 6 Set the date and time on the device please refer to section General menu Date Time Access to device The network analyzer features a front panel with...

Страница 4: ...gs to enter configuration mode press and keys Select the required sub menu with keys and confirm with To exit setup and go back to the readings viewing press The following table show the available sub...

Страница 5: ...atically scaled in order to fit the waveforms on the screen The graph is automatically updated every refresh time selected by the user DISPLAY menu Every page shows the total harmonic distortion THD a...

Страница 6: ...anages the date and time that is used for storage of events for measurements log and for time related functionalities The EMA D6 is equipped with RTC real time clock then the time and date are kept up...

Страница 7: ...s programming and definition refer to setup menu SETPOINT chapter For more information on how the meter handles the setpoint driven alarms refer to the figure below Data logger function The data logge...

Страница 8: ...oint Log Logic expression Password Reset Date Time Utility Display Graphics Editing contacts Transform ratio Time window Frequency DIP SWELL Wiring Convention Type Modality Energy Counter Ethernet LAN...

Страница 9: ...the log memory both events and measurements log 12 ON OFF events Clears the power supply switch ON OFF events 13 Setpoint DO Manual command in order to reset the digital output of the alarm setpoint...

Страница 10: ...V 205000 10000 2000000000 6 Interruption hysteresis mV 275000 10000 2000000000 7 Storage End memory FIFO End memory 1 Threshold active when the voltage is lower than value set 2 The duration of voltag...

Страница 11: ...d capacitive apparent energy 6 10 Set a value of energy meters L2 for active energy imported and exported reactive energy inductive and capacitive apparent energy 11 15 Set a value of energy meters L3...

Страница 12: ...16 daily plans HOLIDAY n n 1 48 UoM Default Range 1 Month holiday January January December 2 Day holiday 1 1 31 3 Plan holiday Daily plan 1 Daily plan 1 16 NOTE HOLIDAY menu supports a maximum of 48...

Страница 13: ...when EMA D6 will be configured as Slave ETHERNET optional UoM Default Range 1 IP Address 10 0 0 100 000 000 000 000 255 255 255 255 2 Subnet mask 255 0 0 0 000 000 000 000 255 255 255 255 3 IP gateway...

Страница 14: ...ulse counter is divided by this coefficient 4 Status on activation of the input Allows reversing the logic of the input function 5 When digital input is using as SP DO reset select the number of setpo...

Страница 15: ...t be compared with limits 5 Used to define the upper threshold 6 Used to define the unit of measure of the upper threshold 7 Used to define the lower threshold 8 Used to define the unit of measure of...

Страница 16: ...e memory is full you can choose to stop the recording End Memory mode or to continue overwriting the oldest records FIFO mode 4 5 6 7 Set the variables driven by date range or and time interval that c...

Страница 17: ...gies Digital inputs Counters Analog input Math 11 Item 2 OFF measures 12 Multiplier 2 1 1 100000 13 Divisor 2 1 1 100000 NOTE this menu is divided into 8 sections for logic expression LE1 8 1 Expressi...

Страница 18: ...neutral voltage VL3 23 A signal COM2 RS 485 optional 6 Phase current IL3 output S2 15 Not used 24 B signal COM2 RS 485 optional 7 Neutral current IN input S1 optional 16 Neutral conductor VN 25 A sign...

Страница 19: ...e phase measuring two conductors without voltage transformers 6 Three phase measuring four conductors balanced multiple loads with one current transformer with three current transformers Connection ty...

Страница 20: ...ransformer Connection type 3X1PH Digital outputs connection L Load F Fuse V 12 250 VAC 150 mA max 10 300 VDC 150 mA max Digital inputs connection Input voltage 24 or 48 or 115 or 230 VAC DC to be defi...

Страница 21: ...ce ph n 1 65 Mohms Power consumption per phase 0 09VA AC current inputs Rated current 1 A or 5 A Measuring range For 1 A scale 10 mA 1 A For 5 A scale 50 mA 5 A Type of input Isolated inputs by intern...

Страница 22: ...5 Ethernet 10BASE T or 100BASE TX auto sensing Connector type RJ45 Protocol supported Modbus TCP Connections Type of terminal Screw fixed Number of terminals 36 Conductor cross section 0 2 2 5 mm2 Tig...