LOG menu
GENERIC
UoM
Default
Range
1
Enable
-
OFF
OFF-Always-Between date-Between hour-
Between date and hour-Trigger
2
Sampling
-
15 min
1-2-3-5-6-10-12-15-20-30 sec
1-2-3-5-6-10-12-15-20-30-60 min
End of day
End of month
3
Storage
-
End memory
End memory / FIFO
4
Start month
-
January
January..December
5
Start day
-
1
1..31
6
Start hour
-
0
0..23
7
Start minute
-
0
0..59
8
End month
-
January
January..December
9
End day
-
1
1..31
10
End hour
-
0
0..23
11
End minute
-
0
0..59
12
Monday
…
Sunday
-
YES
YES-NO
13
Trigger input
-
DI active HIGH
DI active HIGH
DI active LOW
Setpoint
14
DI trigger
-
1
1..4
15
Setpoint trigger
-
1
1..32
16
Source 1..14
-
Internal measures
Internal measures-(measures node 1-20)
17
Group 1..14
-
-
Instantaneous-Average-Energies-Digital input-
Counter-Analog input-Math-Energy TB1..16-
Harmonics VL1..VL3- Harmonics IL1..IL3-
Diagnostic
18
Item 1..14
-
-
OFF-(measures)
1
- Enable or disable the data logger function. Every record is marked with a timestamp taken from the real-time clock.
ALWAYS
- The data logger allows to store at regular intervals up to 14 variables. The recording is continuous (driven only by regular time intervals).
BETWEEN DATE
- The recording allows to store at regular intervals only between a specified date range.
BETWEEN HOUR
- The recording allows to store at regular intervals only in the specified time interval.
BETWEEN DATE AND HOUR
- The recording allows to store at regular intervals between a specified date range and time interval.
TRIGGER
- The recording allows to store at regular intervals driven only by the status of the internal variables (setpoint) or digital input status.
2
- Time interval between a data reading and the next one.
3
- When the memory is full, you can choose to stop the recording (End Memory mode) or to continue overwriting the oldest records (FIFO mode).
4, 5, 6, 7
- Set the variables (driven by date range or/and time interval) that control the starting of the recording.
8, 9, 10, 11
- Set the variables (driven by date range or/and time interval) that control the ending of the recording.
12
- The recording can be disabled for a specific day of the week.
13
- Set the internal variables (setpoint) or digital input status to allows the recording.
14
- Define the number of digital input which controls the starting/ending of the recording.
15
- Define which setpoint controls the starting/ending of the recording.
16
- The data logger allows to store at regular interval up to 14 variables. To configure the data logger, it
’
s necessary to select the source variables (network
analyzer
’
s measures or from external devices).
17
- The data logger allows to store at regular interval up to 14 variables. To configure the data logger, it
’
s necessary to select the group variables.
18
- The data logger allows to store at regular interval up to 14 variables chosen freely among the network analyzer
’
s measures or from external devices.
SMART
UoM
Default
Range
1
Enable
-
OFF
OFF-Always-Between date-Between hour-
Between date and hour-Trigger
2
Sampling
-
15 min
1-2-3-5-6-10-12-15-20-30-60 min
End of day
End of month
3
Storage
-
End memory
End memory / FIFO
4
Group 1..14
-
-
Instantaneous
5
Item 1..14
-
-
OFF-(measures)
NOTE:
the Smart data logger allows to store at regular interval:
1. The instantaneous value that the variable had at the moment of sampling.
2. The average value that the variable had in the sampling period.
3. The maximum value that the variable reached in the sampling period.
4. The minimum value that the variable reached in the sampling period.
Every record is marked with a timestamp taken from the real-time clock.