Continental Hydraulics Installation Manual
Page 7 of 27
CEM-SA-B
CHI 1020687 01/2016
Module Mounting Location:
This module is to be mounted in a cabinet for protection from the local environment.
Ensure there is adequate free space around the module to allow for cooling air flow.
This module is designed to snap onto an industry standard 35mm DIN rail.
Do not mount near other modules that emit high power electrical interference, such as motor
controllers and high power contactors.
Power Supply:
This module is designed to operate on DC power from a regulated power supply ranging from 12
to 30 volts. Match valve solenoid voltage rating to power supply, typically 12 or 24 volts.
A 1 amp medium ac
tion fuse is recommended in the “+” power supply line.
Wiring to Valve:
Two conductors are required for each solenoid. There is no need for shielding on these power
conductors.
Wire size is chosen to provide an acceptable voltage drop between the module and the valve
solenoid. The following chart is based on 5% drop for 12v and 24v applications. The listed cable
length is distance from module to valve, and includes the voltage drop of the return conductor.
Wire size
2.6A 12v
1.6A 24v
0.86A 24v
12 gauge
66 ft. max
215 ft. max
400 ft. max
14 gauge
49 ft. max
159 ft. max
295 ft. max
16 gauge
31 ft. max
100 ft. max
186 ft. max
18 gauge
19 ft. max
63 ft. max
117 ft. max
20 gauge
13 ft. max
39 ft. max
73 ft. max
22 gauge
8 ft. max
25 ft. max
46 ft. max