Troubleshooting
It is assumed that the device is in an operable state and there is communication
between the module and the CHI-PC. Furthermore, the valve control
parameterization has been set with the assistance of the valve data sheets.
FAULT
CAUSE / SOLUTION
ENABLE is active,
the module does
not respond and
the READY LED is
off.
There is presumably no power supply or the ENABLE signal (PIN 8) is not
present.
If there is no power supply, there is also no communication via our operating
program. If a connection has been made to the CHI-PC, then a power supply is
also available.
If the power supply exists, an attempt should be made to see whether the
system can be moved by means of the HAND+ and HAND- inputs (measuring
the output signal to the valve helps).
ENABLE is active,
the READY LED is
flashing.
The flashing READY LED signals that a fault has been detected by the module.
The fault could be:
A broken cable or no signal at the input (PIN 13 or PIN 14), if 4… 20 mA
signals are parameterized.
Internal data error: press the command/SAVE button to delete the data
error. The system reloads the DEFAULT data.
With the CHI-PC operating program the fault can be localized directly via the
monitor.
ENABLE is active;
the READY LED is
on, the system
moves to an end
position.
The control circuit polarity is incorrect. The polarity can be changed with the
POL command or by reversing the connections to PIN 15 and PIN 16.
ENABLE is active,
the READY LED is
on, the STATUS
LED is not on, the
system moves to
the target position
but do
esn’t reach it
(positioning error).
Serious positioning errors can result from incorrect parameterization or
incorrect system design.
Is the cylinder position specified correctly?
Are the deceleration strokes correct (to start the system, the deceleration
distances should be set to approx. 20… 25 % of the cylinder position
12)
?
Is the valve a zero lapped control valve or a standard proportional valve?
In the case of a proportional valve, the valve overlap which may be present
should be compensated for with the MIN parameters. Typical values are to
be found in the valve data sheet.
ENABLE is active,
The system is working and also actuating the valve.
12
The stability criterion of the hydraulic axes must be taken into account.