LIM (Signal monitoring)
Command
Parameters
Unit
Group
FUNCTION
LIM:I
X
i= A|B
x= 0… 2000
0.01%
EXP
A-B
LIM
X
x= 0… 2000
0.01%
EXP
AA
The signal monitoring deactivates the output current and the READY output if the input signal
leaves the permitted range after scaling. This function makes it possible to detect a short circuit or
cable break of a joystick or potentiometer.
Example:
LIM 500 (5% lower/upper limitation) If the input signal gets higher than 95 % or
lower than 5%, it leaves the permitted range and the outputs will switch off.
-100%
working
range
error range for
unipolar signals
error range for
bipolar signals
100%