EN
W415-2344 / A / 11.12.19
9
installation
While the liners must be continuous from the appliance to the chimney cap, to achieve the needed length, they may
be coupled, using an approved coupler.
We recommend that exhaust vents that pass through unheated spaces, such as tall
exterior chimneys, be wrapped in a protective sleeve to minimize condensation and
reverse fl ow symptoms. See the "TROUBLESHOOTING" section for details.
This appliance is approved for use with a 2" (51mm) liner for air intake and a 3" (76mm)
liner for exhaust. For best performance, however, it is recommended to use two 3"
(76mm) liners.
If a 2" (51mm) liner is used for the intake, it may be necessary to adjust the
primary air shutter.
A.
OUTSIDE:
Slip the one end of a liner a
minimum of 2" (51mm) over the sleeve of
the air terminal. Secure using 3 screws.
Then seal the joint and screw heads with
W573-0007 Mill-Pac (not supplied). Repeat
with the other liner.
NOTE: We recommend that the other
end of the exhaust liner be marked
to eliminate the exhaust liner being
connected to the intake collar at the
appliance.
B.
Gently stretch the liners to the required
lengths and insert into the chimney. Trim
and fi t the fl ashing plate to suit the chimney
termination. Place the air terminal onto the
top of the chimney. Make weather tight by
sealing with caulking (not supplied). Fasten
to the chimney with screws and plugs (not
supplied).
C.
INSIDE:
Remove the securing screw from
the front of the vent mounting plate. Pull
the vent mounting plate only, back into
the track, to the front stop. Start the slider
back into position. Re-secure the screw.
The appliance may now be pushed into
its fi nal position inside the wood burning
appliance, and the screw tightened until
the slider has been pulled tight to the front
stop.
D.
Route the fl ex liners through the slider.
Attach and secure the liners to the vent
mounting plate using the same procedure
as before, ensuring that the marked
exhaust liner is attached to the exhaust collar.
FLASHING
PLATE
2” (50.8mm)
OVERLAP
INTAKE
EXHAUST
HIGH TEMP
SEALANT
MOUNTING
PLATE
SECURING
SCREW
INTAKE
EXHAUST
2" (50.8mm)
OVERLAP
MILL-PAC
2" (50.8mm)
LINER
3" (76.2mm)
LINER
SLIDER
REDUCER
CONNECTION
ILLUSTRATED WITH A 2"
(50.8mm) INTAKE LINER.
2.2 chimney
connection
Chimney installation must conform to both national and local code requirements. The chimney must be lined with
one 2" (50.8mm) or 3" (76.2mm) diameter liner for intake and one 3" (76.2mm) diameter liner for exhaust. The
minimum and maximum vent lengths are 10ft (3m) and 35ft (10.7m) respectively. Recommended kits come in 3
lengths:
1-2"Ø (25.4mm-50.8mm) & 1-3"Ø (25.4mm-76.2mm) DOUBLE PLY ALUMINUM LINER-INLET AND
EXHAUST & 2-3"Ø (50.8mm-76.2mm) TO 2"Ø (50.8mm) REDUCERS:
GDI-2320KT VENT KIT 20FT (6.1m)
GDI-2325KT VENT KIT 25FT (7.6m)
GDI-2335KT VENT KIT 35FT (10.7m)
2-3"Ø (50.8mm-76.2mm) DOUBLE PLY ALUMINUM LINER-INLET AND EXHAUST:
GDI-320KT VENT KIT 20FT (6.1m)
GDI-325KT VENT KIT 25 FT (7.6m
GDI-335KT VENT KIT 35 FT (10.7m)