System Reference
56
DAI12-4(FIT)GY
Specifications
Table 6.1. Specifications
Item
Specification
Analog output section
Output format
Bus-isolated voltage/current output
Output range
Voltage: Bipolar ±10V, ±5V
Unipolar 0 - 10V, 0 - 5V (Output voltage ±5mA)
Current: 0 - 20mA
Output impedance
Voltage range: 10
Ω
(Max.)
Output channel
4 channels
Resolution
12 Bits
Conversion accuracy *1
Voltage range±3LSB,
Current range±5LSB
Settling time
Voltage range: 10
µ
sec/ch, Current range: 20
µ
sec/ch
Interrupt
Either IRQ5 or IRQ7 or IRQ9 *2
Internal sampling timer
10
µ
sec - 1,073,741,824
µ
sec *1 *3
Common section
Internal power consumption 5VDC±5% 400mA(Max.)
Maximum distance
of signal extension
1.5m
External dimensions (mm)
25.2(W) x 64.7(D) x 94.0(H) (exclusive of protrusions)
Weight (module itself)
100g
Module connection method
Stack connection by the connector that is provided
with the side of module
Module installation method One-touch connection to 35mm DIN rails
(standard connection mechanism provided in the system)
Applicable wire
AWG 28 - 20
Applicable plug
FK-MC 0,5/12-ST-2,5 (made by PHOENIX CONTACT Corp.)
*1
When the environment temperature is near 0ºC or 50ºC, the non-linearity error may become larger.
*2
Available only when the DAI12-4(FIT)GY is connected to the CPU-SBxx(FIT)GY.
*3
If connected to a DAI12-4(USB)GY, uses the internal timer in the DAI12-4(USB)GY.
The setting range is from 1000 to 1,073,741,000
µ
sec.
Notes!
- When connecting one of the modules to a controller module, the internal power
consumption should be taken into account.
If the total current exceeds the capacity of the power supply unit, the integrity of the
operation cannot be guaranteed.
For further details, please see the Controller Module manual.
- Current output requires an external power supply. With large external power
supply fluctuations (ripple), the conversion precision indicated in the specifications
may not be attainable. If this problem occurs, please use a low-ripple power
supply.
- Depending upon the specific controller module that is used, some of the functions
are not supported.
Содержание DAI12-4FITGY
Страница 1: ...F eIT Series Isolated Analog Output Module DAI12 4 FIT GY User s Manual CONTEC CO LTD...
Страница 47: ...Using the I O Address Map 42 DAI12 4 FIT GY...