18 - Hardware Installation
DeviceMaster PNIO | UP User Guide
: 2000639 Rev. A
Hardware Installation
3.
Use the appropriate method for network attachment of your DeviceMaster 2-
port:
•
PNIO-2102
: Connect the
10/100 port
to the same Ethernet network
segment as the host PC using a standard network cable.
•
PNIO-2302
: Connect either
10/100 port
to the same Ethernet network
segment as the host PC using a standard network cable. You can daisy-
chain another DeviceMaster or Ethernet device to the other Ethernet port.
Note:
If your model provides two Ethernet ports,
E1
is the first port and
E2
is
the second port.
4.
Verify that the
Status
LED has completed the boot cycle and network
connection for the DeviceMaster is functioning using the following table.
Do not connect RS-422/485 devices until the IP address is configured
and an appropriate port interface type has been configured. The
default port setting is RS-232.
5.
Preparing the DeviceMaster for Configuration
on Page 23 for default
network settings and how to configure the DeviceMaster for use.
2-Port with DB9 Connectors LED Descriptions
STATUS
The
STATUS
LED on the device is lit, indicating you have power and
it has completed the boot cycle.
Note:
The
Status
LED flashes while booting and it takes
approximately 15 seconds for the Bootloader to complete the
cycle.
When the Bootloader completes the cycle, the LED
flashes rapidly for several times then stays off and blinks
approximately every 10 seconds when there is no PLC
connection
.
LINK
If the
LINK
(green) LED is lit, it indicates a working Ethernet
connection.
ACT
If the
ACT
(yellow) LED flashes, it indicates network activity.
Note:
For additional LED information, go to the
Caution
Содержание 99531-9
Страница 1: ...PROFINET IO User Guide ...
Страница 60: ...60 Configuring a Serial Port DeviceMaster PNIO UP User Guide 2000639 Rev A Configuring a Serial Port ...
Страница 88: ...88 IO Data Handling DeviceMaster PNIO UP User Guide 2000639 Rev A IO Data Handling ...
Страница 138: ...138 Managing the DeviceMaster DeviceMaster PNIO UP User Guide 2000639 Rev A Managing the DeviceMaster ...
Страница 148: ...148 RedBoot Procedures DeviceMaster PNIO UP User Guide 2000639 Rev A RedBoot Procedures ...